Circuit examples

Application Guide TwinSAFE

135

2.23.3 Calculation

2.23.3.1 PFH / MTTF

d

/B10

d

– values

Component

Value

EL1904 – PFH

1.11E-09

EL2904 – PFH

1.25E-09

Days of operation (d

op

)

230

Hours of operation / day (h

op

)

8

Cycle time (minutes) (T

cycle

)

60 (1x per hour)

Lifetime (T1)

20 years = 175200 hours

2.23.3.2 Diagnostic Coverage DC

Component

Value

EL1904/EL2904

DC

avg

=90%

2.23.3.3 Calculation for block 1

This produces for the calculation of the PFH value for block 1:

PFH

tot

= PFH(EL1904) + PFH(EL2904)

to:

PFH

PFH

PFH

PFH

tot

tot

tot

tot

=

==

=

1.11E-09 + 1.25E-09 = 2.36E

2.36E

2.36E

2.36E----09

09

09

09

The MTTF

d

value for block 1 (based on the same assumption) is calculated with:

1

ܯܶܶܨ

ௗ ௧௢௧

= ෍

1

ܯܶܶܨ

ௗ ௡

௜ୀଵ

as:

1

ܯܶܶܨ

ௗ ௧௢௧

=

1

ܯܶܶܨ

(ܧܮ1904) +

1

ܯܶܶܨ

(ܧܮ2904)

If only PFH values are available for EL1904 and EL6900, the following estimation applies:

ܯܶܶܨ

(ELxxxx) =

(1 െ ܦܥ(ܧܮݔݔݔ))

ܲܨܪ(ܧܮݔݔݔ)

Hence: