2 block formation and safety loops, 3 calculation – BECKHOFF TwinSAFE User Manual

Page 71

Advertising
background image

Circuit examples

Application Guide TwinSAFE

69

EL2904 (applies to all EL2904 used)

Parameter

Value

Current measurement active

Yes

Output test pulses active

Yes

2.11.2 Block formation and safety loops

2.11.2.1 Block 1

2.11.3 Calculation

2.11.3.1 PFH / MTTF

d

/B10

d

– values

Component

Value

EL1904 – PFH

1.11E-09

EL2904 – PFH

1.25E-09

EL6900 – PFH

1.03E-09

S1 – B10

d

2,000,000

S2 – B10

d

2,000,000

Restart - B10

d

10,000,000

Lock – B10

d

100,000

Unlock – B10

d

100,000

K1 – B10

d

1,300,000

K2 – B10

d

1,300,000

Tumbler – B10

d

2,000,000

Days of operation (d

op

)

230

Hours of operation / day (h

op

)

16

Cycle time (minutes) (T

cycle

)

15 (4x per hour)

Lifetime (T1)

20 years = 175200 hours

EL1904

Restart

S1

S2

Lock

UnLock

EL2904

tumbler

EL1904

EL6900

K1

K2

EL2904

Advertising