Circuit examples

68

Application Guide TwinSAFE

2.11 Protective door function with tumbler (Category 4, PL e)

The protective door has two contacts, S1 ‘door closed’ and S2 ‘door closed and locked’, which are wired
to safe inputs of an EL1904. The testing of the inputs is active. Checking of the signals for discrepancy
cannot take place, because there is no temporal relationship between the signals. The feedback loop and
the restart signal are read via a safe input. The testing of the inputs is active. The contactors K1 and K2
are connected in parallel to the safe output. Current measurement and testing of the output are active for
this circuit.
The tumbler is switched via 2 safe inputs in which testing is active. Testing and current measurement is
active on the safe output for the tumbler.

CLOSED

OPEN

K1

K2

Unlock

Lock

Restart

S1

S2

Logical connection in

the EL6900

K1

K2

2.11.1 Parameters of the safe input and output terminals

EL1904 (applies to all EL1904 used)

Parameter

Value

Sensor test channel 1 active

Yes

Sensor test channel 2 active

Yes

Sensor test channel 3 active

Yes

Sensor test channel 4 active

Yes

Logic channel 1 and 2

Single Logic

Logic channel 3 and 4

Single Logic