2 circuit examples, 1 estop function variant 1 (category 3, pl d) – BECKHOFF TwinSAFE User Manual

Page 9

Advertising
background image

Circuit examples

Application Guide TwinSAFE

7

2 Circuit examples

2.1 ESTOP function variant 1 (Category 3, PL d)

The emergency stop button is connected via two break contacts to an EL1904 safe input terminal. The
testing and monitoring of the discrepancy of the two signals are activated. The restart and the feedback
signal are wired to standard terminals and are transferred to TwinSAFE via standard PLC. The contactors
K1 and K2 are connected in parallel to the safe output. Current measurement and testing of the output
are active for this circuit.

2.1.1

Parameters of the safe input and output terminals

EL1904

Parameter

Value

Sensor test channel 1 active

Yes

Sensor test channel 2 active

Yes

Sensor test channel 3 active

Yes

Sensor test channel 4 active

Yes

Logic channel 1 and 2

Single Logic

Logic channel 3 and 4

Single Logic

EL2904

Parameter

Value

Current measurement active

Yes

Output test pulses active

Yes