Circuit examples

Application Guide TwinSAFE

49

2.8 Protective door function variant 1 (Category 3, PL d)

The protective door uses a combination of break and make contacts on the safe inputs of an EL1904. The
testing of the inputs is active and the signals are tested for discrepancy (200 ms). The feedback loop is
read via a standard input and transferred to TwinSAFE via the standard PLC. The contactors K1 and K2
are connected in parallel to the safe output. Current measurement and testing of the output are active for
this circuit.

2.8.1

Parameters of the safe input and output terminals

EL1904 (applies to all EL1904 used)

Parameter

Value

Sensor test channel 1 active

Yes

Sensor test channel 2 active

Yes

Sensor test channel 3 active

Yes

Sensor test channel 4 active

Yes

Logic channel 1 and 2

Single Logic

Logic channel 3 and 4

Single Logic

EL2904

Parameter

Value

Current measurement active

Yes

Output test pulses active

Yes