5 estop function variant 5 (category 4, pl e) – BECKHOFF TwinSAFE User Manual

Page 33

Advertising
background image

Circuit examples

Application Guide TwinSAFE

31

2.5 ESTOP function variant 5 (Category 4, PL e)

The emergency stop button with two break contacts, the restart and the feedback loop are connected to
safe channels of an EL1904 input terminal. The testing of the signals is activated. The two emergency
stop signals are tested for discrepancy. Contactors K1 and K2 are wired to different output channels. The
A2 connections of the two contactors are fed together to ground. The current measurement of the output
channels is deactivated for this circuit. The testing of the outputs is active.

2.5.1

Parameters of the safe input and output terminals

EL1904 (applies to all EL1904 used)

Parameter

Value

Sensor test channel 1 active

Yes

Sensor test channel 2 active

Yes

Sensor test channel 3 active

Yes

Sensor test channel 4 active

Yes

Logic channel 1 and 2

Single Logic

Logic channel 3 and 4

Single Logic

EL2904

Parameter

Value

Current measurement active

No

Output test pulses active

Yes