6 clearing block configuration errors – Flowserve 3400IQ Digital Positioner User Manual

Page 109

Advertising
background image

0

Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07

flowserve.com

10.6 Clearing Block Configuration Errors

Clearing Block Configuration Errors
Table 10.8 and Table 10.9 list the parameters in the AO and PID blocks which can cause the status
bit of block configuration error to be set in their respective BLOCK_ERR parameters. The tables also
provide the initial values and the valid range for the parameters.

NOTE: Block configuration errors can only be cleared if the function block is being executed
(running). One way of determining block execution is by doing a series of two or three reads of the
BLOCK_TEST parameter and confirming that the first byte of the parameter is incrementing. This will
work if the execute rate is fast relative to the speed of reading BLOCK_TEST. A very slowly executing
block may not appear to execute because block parameters are updated only when the block
executes.

Table 10.8 AO Block Parameters

Parameter

Initial Value

Valid Range

Corrective Action

ALERT_KEY

0

non-zero

Initial value is a configuration

error. Set value to non-zero

number.

SIMULATE

1 (disabled)

1-2 (disabled -enabled)

Set value in valid range.

XD_SCALE

0 to 100

EU_100 > EU_0, UNITS_

INDEX matches output of

transducer block

Set values to valid range(s).

CHANNEL

0

1-2

Initial value is a configuration

error. Set value to valid range.

SP_RATE_DN

SP_RATE_UP

+INF

0-15

Set value to valid range.

SP_HI_LIM,

100

0-100

Set value to valid range.

SP_LO_LIM

0

0-100

Set value to valid range.

SHED_OPT

0

1-8 (see Shed Options in the

FF specs.)

Initial value is a configuration

error. Set value in valid range.

BYPASS

0

1:OFF, 2:ON

Initial value is a configuration

error. Set value in valid range.

SHED_OPT

0

1-8 (see Shed Options in the

FF specs.)

Initial value is a configuration

error. Set value in valid range.

HI_HI_LIM HI_LIM

+INF
+INF

PV_SCALE, +INF

Values must be set in rank order

(e.g. LO_LIM > LO_LO_LIM but <

HI_LIM etc.)

LO_LIM LO_LO_LIM

-INF

-INF

PV_SCALE, -INF

Values must be set in rank order.

OUT_HI_LIM

OUT_LO_LIM

100

0

OUT_SCALE +/- 10%

Verify that OUT_HI_LIM >

OUT_LO_LIM.

SP_HI_LIM SP_LO_LIM

100

0

PV_SCALE +/- 10%

Verify that SP_HI_LIM >

SP_LO_LIM.