3 calibration – Flowserve 3400IQ Digital Positioner User Manual

Page 98

Advertising
background image

Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07



3. Press and hold the Re-Cal button for at least five seconds to initiate the stroke calibration. (NOTE:

The transducer block must be out-of-service before the Re-Cal button will be active.) If Auto Tune
is selected, this will also auto tune the positioner response.

4. Replace cover and return to operation. (Refer to Logix 3400IQ Digital Positioner IOM for more

details.)

9.3 Calibration

The output position of the Logix 3400IQ digital positioner is calibrated using the transducer block
CALIBRATE parameter. The positioner performance must be verified by the operator.

Calibration Parameters
Table 9.1 lists transducer block parameters and their values used in the calibration procedures.

Table 9.1 Transducer Block Calibration Parameters

Two-point Calibration

The Logix 3400IQ digital positioner has two-point calibration. The stroke position feedback poten-
tiometer and the actuator pressure transducers are calibrated this way. The positioner must be
pre-configured to the proper air action, valve type (linear or rotary), positioner model (standard or
advanced) before the calibration is done. (CONTROL_FLAGS =16 -> Air to Open, Linear, Advanced =
default values)

Parameter

Description

Value - Meaning

Comments

MODE_BLK The operating mode of

the transducer block

Permitted modes:

The transducer block must be in the OOS

mode to perform Logix 3400IQ digital

positioner calibration.

Auto — Auto (target mode)
OOS — Out of Service

CALIBRATE

One-byte value which

selects the calibration

operation to be per-

formed.

0 Normal operation. Valve tracks Calibration and correction commands are

executed when the command is written.

FINAL_VALUE

1 Initiates stroke calibration. Closes
valve.
2 Initiates actuator pressure
transducers calibration.
3 Moving valve to closed position

Messages only

4 Moving valve to open position
5 Calibrating Supply
6 Calibrating actuator sensor

- closed
7 Calibrating actuator sensor - open
8 Monitoring of Re-Cal button.
9 Error occurred during calibration
10 Inner-loop offset adjustment

Nulls the spool block

11 Auto Tune Positioner

Only active when Re-Cal is done

12 JogCal - Waiting for user to set point

Initiates the monitoring of the button for

five seconds

13 Range Checking
14 Normal Operation (Rev 0x23).

Checkjog call setting in

MISC_FLAGS

Jog Cal must be enabled in MISC_FLAGS

before it can be initiated

PRES_CAL

Input supply pressure

for calibration

0 – 150 psig max.

Used to calibrate the span of the actuator

pressure sensors