Fail-safe Handling
The fail-safe parameters determine the response of an output block to the following conditions.
FSTATE_TIME is the number of seconds without communication or with Initiate Fail Safe at the
CAS_IN status, required to put this block into the fail safe state. The FAULT_STATE parameter of the
resource block may also put this block into the fail safe state. The Failsafe Type I/O option determines
whether the action is simply to hold, or to move to FSTATE_VAL.

The Target to Manual if IFS I/O option may be used to latch the fail safe state when IFS appears in the
CAS_IN status. This will cause a fail-safe block alarm. After the cause of the IFS status is removed,
the target mode may be returned manually to CAS mode when it is safe to do so.

AO Block Parameter List
Table 8.7 lists the block parameters and default values for the AO function block.

Table 8.7 AO Function Block Parameter List

Block
Index

Name

Store
Type

Data Type
(Units)

Valid
Range

Write Restrictions

Default Value

1

ST_REV

S

Unsigned16

Read Only

0

2

TAG_DESC

S

Octet String

All spaces

3

STRATEGY

S

Unsigned16

0

4

ALERT_KEY

S

Unsigned8

0

5

MODE_BLK

Mix

MODE_BLK

Target = OOS

Permitted = OS + MAN

+ AUTO + CAS + RCAS

Normal = AUTO

6

BLOCK_ERR

D

Bit String

Read Only

7

PV

D

ANALOG (PV)

Read Only

8

SP

N

ANALOG (PV)

PV_SCALE,

+/- 10%

Target mode must be AUTO,

CAS or RCAS, not permitted

during cascade initialization,

tracking cannot be operative.

9

OUT

N

ANALOG (XD)

XD_SCALE,

+/- 10%

Target mode must be Man

or OOS

10

SIMULATE

D

SIM_FLOAT

Enable = OFF

11

PV_SCALE

S

SCALING

Actual mode must be Man

or OOS

0 – 100

12

XD_SCALE

S

SCALING

Actual mode must be Man

or OOS

0 – 100

13

GRANT_DENY

D

ACCESS_

PERM_T

14

IO_OPTS

S

Bit String

Target mode must be OOS

0

15

STATUS_OPTS

S

Bit String

Target mode must be OOS

0

16

READBACK

D

ANALOG (XD)

Read Only

17

CAS_IN

N

ANALOG (PV)

18

SP_RATE_DN

S

Float (PV /

seconds)

Positive

+INF

19

SP_RATE_UP

S

Float (PV /

seconds)

Positive

+INF

20

SP_HI_LIM

S

Float (PV)

PV_SCALE,

+/- 10%

100

21

SP_LO_LIM

S

Float (PV)

PV_SCALE,

+/- 10%

0

22

CHANNEL

S

Unsigned16

Must be 1

Target mode must be OOS

0

23

FSTATE_TIME

S

Float (seconds)

Positive

0

24

FSTATE_VAL

S

Float (PV)

PV_SCALE,

+/- 10%

0

25

BKCAL_OUT

D

ANALOG (PV)

Read Only

26

RCAS_IN

N

ANALOG

(PV)

27

SHED_OPT

S

Unsigned8

1 to 8

0

28

RCAS_OUT

D

ANALOG (PV)

Read Only

29

UPDATE_EVT

D

EVENT

30

BLOCK_ALM

D

ALARM_

DISCRETE

32

WSP*

D

ANALOG (PV)

Advertising