Flowserve 3400IQ Digital Positioner User Manual

Page 88

Advertising
background image

Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07



Table 8.23 System Management Supported Features

SM_SUPPORT bit Feature

Supported?

0

Set physical device tag (agent)

yes

1

Set field device address (agent)

yes

2

Clear address (agent)

yes

3

Identify (agent)

yes

4

Locating function blocks (agent)

yes

5

Set physical device tag (manager)

no

6

Set field device address (manager)

no

7

Clear address (manager)

no

8

Identify (manager)

no

9

Locating function blocks (manager)

no

10

FMS server role

yes

11

Application clock synch (time slave)

yes

12

Scheduling function block

yes

13

Application clock synch (time publisher)

no

14

to 31 Reserved for future use.

no

SM_SUPPORT Bits
Any bit (of the object SM_SUPPORT) will be set that corresponds to a supported feature listed in
Table 8.23.

The resulting value in the object SM_SUPPORT is 1C1F (hex).

SM Agent Objects
Four SM agent objects are contained in the SMIB object dictionary. One object, SM_SUPPORT, was
described previously. The three other objects are timers associated with SM operations. Table 8.24
identifies the SM Agent objects with their object directory index and default values.

Table 8.24 SM Agent Objects

Object

Description

OD
Index

Default Value

SM_SUPPORT Variable that indicates the features supported by SM

in this device. See Table 8.22, Logix 3400IQ Digital

Positioner SMIB Object Dictionary

258

0x1C1F

T1

Value of the SMstep timer in 1/32 of a millisecond

ticks.

259

96,000* (3 seconds)

T2

Value of the SM set address sequence timer in 1/32 of

a millisecond ticks.

260

1,920,000* (60

seconds)

T3

Value of the SM set address wait timer in 1/32 of a

millisecond ticks.

261

480,000 * (15 seconds)

* The default value is specified by the communications profile for the application area

System Application Clock Time Synchronization
Each link in a fieldbus network contains an application clock time publisher responsible for distrib-
uting application time on the link.

A clock synchronization message is periodically sent by the time publisher to all fieldus devices. The
application clock time is independently maintained in each device based on its own nternal crystal clock.

Clock synchronization provides the capability for devices to time stamp data (events and alarms when
they occur).