9 configuration tasks – Flowserve 3400IQ Digital Positioner User Manual

Page 37

Advertising
background image

37

Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07

flowserve.com

Table 6.4 Logix 3400IQ Digital Positioner Identification

Step

View Parameter

Verify

1

RS.DEV_TYPE

The Logix 3400IQ digital positioner is the proper device type:

For the Logix 3400IQ digital positioner, the value is = 0x0202

2

RS.REVISION_ARRAY

The revision number of the:

REVISION_ARRAY =
REVISION_ARRAY =
REVISION_ARRAY =

Fieldbus board boot code (0x204)
Fieldbus board boot code (Not critical)
Positioner board firmware (0x0024 or 0x0025)
NOTE: These numbers are helpful when troubleshooting the device.

3

Physical Device Tag
NOTE: The device tag name is

not contained in a parameter.

It can be set and viewed

using the fieldbus device

configurator application.

The physical device tag is correct.

6.9 Configuration Tasks

Device Configuration Procedure Overview

A typical device configuration consists of the following tasks listed in Table 6.5 using the NI-FBUS

Configurator application. Details on using the configurator application are found in the NI-FBUS

Configurator user manual supplied with the application software.

This procedure assumes that the hardware installation of the Logix 3400IQ digital positioner is

complete and the Logix 3400IQ digital positioner is powered up.

Table 6.5 Logix 3400IQ Digital Positioner Configuration Task List

Task

Procedure

Result

1

Start the fieldbus process application

Scans the fieldbus network and provides a listing

of all active fieldbus devices on the network or

selected link.

2

Start the fieldbus configurator application

Configurator windows are displayed on screen

listing the active fieldbus devices.

3

Select a fieldbus device for configuration

4

Change the device and block tags, if

desired.

Any unassigned tags are given a default tag name

by the configurator.

5

Select/add/edit function blocks to create a

function block application process.
NOTE: Configure block objects in the

following order:
1. Resource block
2. Transducer block
3. Analog Output block
4. PID block

Shows a representation of function blocks in the

graphical interface window.

6

Connect (or wire) function blocks to

define process loops.

Linkages between function block inputs and outputs

are created by using wiring tools. Pre-configured

templates can also be used.

7

Change block parameters, if necessary.

Parameters changed for the process requirements.

8

Configure trends and alarms

Trending and alarms configured according to the

process requirements.

9

Adjust the block execution schedule.

The function block execution schedule changed

according to the process requirements.