2

VCR Attributes
The attributes for the VCR types (VCR name) defined in the Logix 3400IQ digital positioner device are
standard fieldbus attributes. There are 16 available VCR‘s available in the Logix 3400IQ. For detailed
descriptions of these attributes, see

Unsupported Services
The following is a list of services which are not supported (not used) in the Logix 3400IQ digital
positioner FBAP:

FB_Action (all function blocks are static)

Put_OD (all ODs are static)

Domain upload

Program invocation

Reception of alert and trend indications

Access protection and check of password

AlertEventConditionMonitoring

Write to variable lists

Create/Modify/Delete variable lists

Read and write access by name

PhysRead, PhysWrite

ReadWithType, WriteWithType

InformationReportWithType

8.20 Logix 3400IQ Digital Positioner Variable

Enumeration

The following list defines the Logix 3400IQ digital positioner variables enumeration.

CALIBRATE: This variable initiates calibration procedures, and reports current state of calibration
during the procedure.

Value

Function

0

Normal operation, position control enabled

1

Automatically calibrate stroke, Re-Cal stroke

2

Automatically calibrate actuator pressure sensors

*5

Moving valve to closed position, get feedback at 0%

*6

Moving valve to open position, get feedback at 100%

*7

Calibrating SUPPLY sensor

*8

Moving valve to closed position, calibrating actuator sensor

*9

Moving valve to open position, calibrating actuator sensor

*11

Check that Re-Cal button is depressed

*12

Error occurred during calibration

*16

Automatically determine inner-loop offset

18

Perform step time test

* Read-only — user cannot send CALIBRATE in this mode.