Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07

flowserve.com

Table 10.16 Transducer Block Signature Parameters

Parameter

Description

Value-Meaning

Comments

MODE_BLK

The operatingmode of the

transducer block

Permitted Modes: Auto - Auto

(target mode) OOS - Out of

Service

The transducer block must be

in the OOS mode to perform a

signature

SIG_FLAGS

Byte values which select

which signature options

are used

0 - VALVE INIT Initializes

valve for signature

capture. Read-only

1 - STEP_RAMP Selects

which type of signature is

desired. Select for ramp

signature.

2 - SIG_COMPLETE Status

byte set when the signa-

ture has been completed,

Read-only

4 - PRESS_MEAS Selects if

actuator pressure read-

ings are desired as part of

the signature. Select for

readings

5 - BEGIN_SIG Set to initiate

the signature routine.

Select the desired signature

options and then make sure the

signature parameters are set

to the desired operation before

beginning the signature.

SIG_START

Beginning position point

(%) for signature -10% to

110% position range

Set higher than the stop

position for a valve closing

signature.

SIG_STOP

Ending position point (%)

for signature

-10% to 110% position range Set lower than the starting

position for a closing signature

RAMP_RATE* Desired rate (% per

Minute) for ramp

%/Min. Minimum value is 1.0 Typically this is set to 100.

Very long times could result in

completely filling the 10K RAM

buffer. Can only be set when

STEP_RAMP in SIG_FLAGS has

been selected.

SAMPLE_

TIME

Data acquisition time

between samples

Seconds. Range 0.1 to 2.55.

Set to a valid value before

running signature. Typically

0.1

Determines the number of data

points stored in the signature.

STEP_TIME*

Delay time after step

Seconds. Range 0-650.0

Typically set to 0.1

Allows settling time to capture

valve response to the step. Can

only be set when STEP_RAMP in

SIG_FLAGS is not selected.

SIG_INDEX

Pointer used for data

transfer

Write the desired packet

value.

Writing a value between 1

and the max number shown

in SIG_COUNTER moves that

packet of data into the SIG_DATA

array for retrieval.

SIG_

COUNTER

Indicates number of data

points collected

Increments by 1 as each data

packet is collected

SIG_DATA

Array for the storage and

transfer of signature data

Order of data is: Command (%)

Position (%) Port 2 pressure

Port 1 pressure

STROKE_

TSTPSI

Supply pressure in PSI

for stroke test

150 psi max.