Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07

22

Table 10.16 Transducer Block Signature Parameters

Parameter

Description

Value-Meaning

Comments

STROKE_

OPENTIM

Stroking time during

opening

Seconds

Determined during the last

stroke calibration where the Step

Time Test option was ran

STROKE_

CLOSEDTIM

Stroking time during

closing

Seconds

Determined during the last

stroke calibration where the Step

Time Test option was ran

* Special Note: Because of the internal Database size limit of 10K within the Fieldbus device, the values for

RAMP_RATE or STEP_TIME may be recalculated to the most reasonable value to allow using the database.

The new value will appear in the parameter after the desired one is written. This is done to prevent accidental

overflow of the database.
It is still possible that the database may overflow, because of timing constraints. If this should happen,

SIG_COMPLETE will not appear, but BEGIN_SIG will be turned off. BLOCK_TEST element 6 will be set to 10

(0x0a) as an error indication. Since this does not affect operation of the positioner itself, no actual error will be

reported over Fieldbus.