5 transducer block – Flowserve 3400IQ Digital Positioner User Manual

Page 46

Advertising
background image

Logix 3400IQ Digital Positioner FCD LGENIM3402-00 – 0/07

4

8.5 Transducer Block

Transducer Block Function
The transducer block de-couples (or insulates) function blocks from local I/O devices, such as
sensors or actuators. In the Logix 3400IQ digital positioner, the transducer block takes the position
from the analog output block and sends it, along with other parameters, to the positioner subsystem.

Transducer Block Parameters
Table 8.5 lists the FF and Valtek product-defined parameters and their default values in the transducer
block.

Table 8.5 Transducer Block Parameters

In-

dex

Fieldbus Parameter Name

Fieldbus

Datatype

Storage

Read/ Write

Access

Type

Notes, Default

Values

1

ST_REV

Unsigned16 S

R

FF Parameter, 0

2

TAG_DESC

Octet String S

R/W

FF Parameter,

blanks

3

STRATEGY

Unsigned16 S

R/W

FF Parameter, 0

4

ALERT_KEY

Unsigned8

S

R/W

FF Parameter, 1

5

MODE_BLK

DS-69

Mixed

R/W

FF Parameter,

OOS

6

BLOCK_ERR

Bit String

D

R

FF Parameter

7

UPDATE_EVT

DS-73

D

R

FF Parameter

8

BLOCK_ALM

DS-72

D

R/W

FF Parameter

9

TRANSDUCER_DIREC-

TORY

Unsigned16 S

R

FF Parameter

10

TRANSDUCER_TYPE

Unsigned16 S

R

FF Parameter

11

XD_ERROR

Unsigned8

D

R

FF Parameter

12

COLLECTION_DIRECTORY Unsigned32 S

R

FF Parameter

13

FINAL_VALUE

DS_65

N

R/W*

Std

Write restricted to

AO OOS

14

FINAL_VALUE_RANGE

DS-68

S

R/W

FF Parameter

15

FINAL_VALUE_CUTOFF_HI float

S

R/W*

Info-1

110

16

FINAL_VALUE_CUTOFF_LO float

S

R/W*

Info-1

1

17

FINAL_POSITION_VALUE

DS_65

N

R

Std

18

ACT_FAIL_ACTION

Unsigned8

S

R

Not used – see

FAIL_MODE

19

ACT_MAN_ID

Unsigned8

S

R/W

FF Parameter

20

ACT_MODEL_NUM

Visible

String

S

R/W

FF Parameter

21

ACT_SN

Visible

String

S

R/W

FF Parameter

22

VALVE_MAN_ID

Unsigned8

S

R/W

FF Parameter

23

VALVE_MODEL_NUM

Visible

String

S

R/W

FF Parameter

24

VALVE_SN

Visible

String

S

R/W

FF Parameter,

FLWSERVE

25

VALVE_TYPE

Unsigned8

S

R/W

FF Parameter

26

XD_CAL_LOC

Visible

String

S

R/W

FF Parameter

27

XD_CAL_DATE

Visible

String

S

R/W

FF Parameter, Ori-

ginal type “Date”

is Y2K compatible

28

XD_CAL_WHO

Visible

String

S

R/W

FF Parameter

Manufacturer Specific Parameters — Owned by Logix Control Processor
29

DAC_PERCENT

float

D

R

Std

30

CONTROL_FLAGS

Bit String

N

R/W*

Std

31

GAIN_UPPER

float

S

R/W*

Std

2

32

GAIN_LOWER

float

S

R/W*

Std

1

Advertising