10.14 Signature Procedure

The following steps are an example of how to initiate a ramp signature capture.

1. Make sure the process is in a safe condition and notify the control room that the valve will

temporarily be taken off-line.

2. Verify preparedness to proceed.

3. Put the Transducer block MODE_BLK OOS

4. Set SIG_START to desired value.

5. Set SIG_STOP to desired value.

6. Set SAMPLE_TIME to desired value. (Typically 0.1)

7. In SIG_FLAGS, select; STEP_RAMP, PRESS_MEAS.

8. Write values to the Logix 1400 digital positioner.

9. Set RAMP_RATE to desired value. (Typically 100)

10. Write value to the Logix 1400 digital positioner.

11. In SIG_FLAGS, select BEGIN_SIG.

12. Write value to the Logix 1400 digital positioner.