Lower the nozzle hook, shutting the unit off – Gasboy Atlas Start-up User Manual
Page 167

MDE-4334D Atlas™ Start-up and Service Manual · July 2013
Page 6-47
Hanging Hardware
Hydraulic/Mechanical Components
To test the hose and hanging hardware continuity, proceed as follows:
1
Ensure that there is no liquid fuel or flammable vapor present. Clean up, as required.
2
Lift the nozzle hook and authorize the unit to pressurize the hose.
3
Lower the nozzle hook, shutting the unit off.
Figure 6-24: Testing Hanging Hardware Continuity
Note: Use only a low voltage digital Ohmmeter to
perform this test. Do not use a Megger tester.
Digital Ohmmeter
Side Dispensing Unit
Front Dispensing Unit
A= Maintain at least 18 inches
above the ground and away from
the unit during the test
Note: When testing any unit, the A measurement of
18 inches applies whether the unit is a FRONT or
SIDE Dispensing unit.
A
A
Test Clip
Nozzle
Swivel
Breakaway
Outlet Casting
Test Clip
Hose