CFN Series System
4-8
05/28/03
TOKHEIM 330B, 333B-SA, TCS, AND PREMIER INTERFACE
Electronic Interface
Basic System
1 to 16 Hoses System consists of one Site Controller II, one interface box, and one C05578
cable and Tokheim Splitter combination.
17 to 32 Hoses System consists of one Site Controller II, two interface boxes, and one C05876
cable and Tokheim Splitter combination.
NOTES:
1.
All Tokheim equipment should be installed per Tokheim specifications.
2.
Wiring trough, conduits, and wire are furnished by the installer.
3. A Model 180 signal cable extension is available as an accessory from Tokheim. The
maximum distance of the combined cables should not exceed 350 feet. The maximum
distance for a 94 or 98 interface box is 250 feet.
4.
A Model 68 Box is recommended for emergency shut-off applications.
5.
Communication for pumps 1-32 may be provided through port 1 or 3 of the Site Controller II.