7.6 Replacing the press plunger

In order to facilitate replacing the press plunger, the following
procedure is recommended.

1. Remove the screw (20) and the press drive cover (56) while the

furnace head is closed.

2. Loosen the terminal screw (65) from the press plunger by about

half a rotation.

3. Open the furnace head by means of the respective key (90). Once

the furnace head is wide open, switch off the furnace, disconnect
the power, and allow the furnace to cool to room temperature.

4. Push the press plunger (59) with slightly rotating movements into

the firing chamber with one hand and pull from below with the
other hand.

Contraindication:

Do not touch the thermocouple when replacing the press
plunger.

5. Push the white press plunger

(59) with the taper ahead into
the guide bush. Push the press
plunger with slightly rotating
movements into its split taper
socket (64) and fasten the screw
(65).

Contraindication:
Never reach into the press drive during

operation. There is a risk of burn
hazard and crushing.

Mount the press drive cover (56) and fasten with screw.

6. Connect the power plug and switch on the furnace with the I/O

switch.