Wiring, Modgas-x field technical guide 10, Warning – Orion System MODGAS-X User Manual

Page 10

Advertising
background image

WIRING

MODGAS-X Field Technical Guide

10

Two Modulating Valves & Up To 13 Stages Fixed Heat - Stand-Alone

Two Modulating Valve With Up To 13

Additional Stages Of Fixed Heat

Stand-Alone Wiring, Continued

If communication is lost to the 12-Relay E-BUS Expansion Module,
the 12-Relay E-BUS Expansion Module will turn off its relays and

the MODGAS-X Controller will alarm and fall back to using only
its onboard stages. If communications is restored, the MODGAS-X
Controller will begin staging up if needed.

Figure 7: Two Modulating Valves & 13 Stages of Fixed Heat - 12-Relay E-BUS Expansion Module

12-Relay E-BUS

Expansion Module

RLY9

R1

R5

RLY10

R2

R6

RLY11

R3

R7

RLY12

R4

R8

EBC E-BUS Cable

Connect To MODGAS-X Controller

24 VAC

GND

15 VA Minimum

Power Required

WARNING!!

Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result in damage to
one or more of the boards. Expansion Modules must be wired in such a way that the expansion modules and the controller are always
powered together. Loss of power to the expansion module will cause the controller to become inoperative until power is restored to the
expansion module.

Note:
All Relay Outputs Are Normally Open
And Rated For 24 VAC Power Only.
1 Amp Maximum Load.

RLY9

RLY10

RLY11

RLY12

RLY-COM

MADE IN USA

RLY-COM

RLY-COM

RLY1

RLY2

RLY3

RLY4

RLY8

RLY7

RLY6

RLY5

24VAC

GND

EXPANSION BOARD

YS102324 REV 2

RELAY

24 V

A

C

GND

RLY1
RLY2
RLY3
RLY4

COM

COM

RLY5
RLY6
RLY7
RLY8

COM

Heat Stage 4 (Fixed)
Heat Stage 5 (Fixed)
Heat Stage 6 (Fixed)
Heat Stage 7 (Fixed)

Heat Stage 8 (Fixed)
Heat Stage 9 (Fixed)

Heat Stage 10 (Fixed)
Heat Stage 11 (Fixed)

Heat Stage 12 (Fixed)
Heat Stage 13 (Fixed)
Heat Stage 14 (Fixed)
Heat Stage 15 (Fixed)

R9
R10
R11

R12

Revised 9/30/14

Advertising