Appendix b, Modgas-x replacement of modgas ii, Modgas-x field technical guide – Orion System MODGAS-X User Manual

Page 25: Replacing the modgas ii with the modgas-x

Advertising
background image

MODGAS-X Field Technical Guide

APPENDIX B

25

MODGAS-X Replacement of MODGAS II

Replacing the MODGAS II with the

MODGAS-X

The retrofi t replacement involves a few easy steps. Refer to Figure
13, below
.

WARNING: Do Not Connect Power To VOUT/Ground
Terminal Block!

STAND-ALONE MODE OPERATION

Step 1: Disconnect power from the MODGAS II Controller.

Step 2: Disconnect the Supply Air Temperature Sensor from the

MODGAS II and wire it to the MODGAS-X. If the Supply

Air Temperature Sensor is being shared with a Stand-
Alone MHGRV Controller, maintain the same wiring
with

the

MHGRV

Controller.

Step 3: Wire all other inputs and outputs per Figure 2, page 5.

Step 4: Set the SAT Options Jumper per Table 8, page 24.

Step 5: Connect power to the MODGAS-X Controller.

COMMUNICATIONS MODE OPERATION

Step 1: Disconnect power from the MODGAS-X Controller.

Step 2: The Supply Air Temperature Sensor needs to remain
installed on whatever controller it is currently on. If it
is currently installed on the MODGAS II Controller, then
reinstall it on the MODGAS-X Controller.

Step 3: Set the SAT Options Jumper per Table 9, page 24.

Step 4: Connect power to the MODGAS-X Controller.

Figure 13: MODGAS-X Controller

MODGAS-X CONTROLLER

(OE377-26-00058)

WARNING!: Do
Not Connect
Power To The
VOUT/Ground
Terminal Block!

I C Cable

Connects To

Main Controller’s

Expansion

Port

2

See Tables 8 & 9, Page 24

For

Settings.

Only One Supply Air
Temperature Sensor

Can Be Used Per Application.

SAT OPTIONS

Jumper

See Table 7, Page 24

For Connection Settings.

Advertising