LCD DISPLAY SCREENS
MODGAS-X Field Technical Guide
18
Setpoint & Force Screens
Setpoint Screens
Refer to the following map when navigating through the Set-
point Screens. From the SETPOINTS Screen, press
<ENTER>
to scroll through the screens and change setpoints. Use the
<UP>
and
<DOWN>
arrow keys to change your selections. Then press
<ENTER>
to save the new setpoint.
NOTE: When the MODGAS-X is operating in
Communications Mode, these setpoint screens
will not appear on the LCD display because
they are controlled by the Main Controller.
SETPOINTS
SAT SP
40-200°F
5-93°C
RESET SP
40-200°F
5-93°C
HEATING SUPPLY AIR TEMPERATURE SETPOINT
This is the target temperature while the heating is enabled. If you are
using the reset signal, this is the setpoint it will calculate to at zero volts.
Will display only in stand-alone mode.
The SAT Setpoint is set by the LCD Display in stand-alone mode and is
set by the Main Controller in communicating mode.
Minimum
Default
Maximum
40°F
5°C
120°F
49°C
200°F
93°C
RESET HEATING SUPPLY AIR SETPOINT
This is the maximum temperature at which the Supply Air Temperature
will reset to. Will display only in stand-alone mode.
The Reset Setpoint is set by the LCD Display in stand-alone mode and
is set by the Main Controller in communicating mode.
Minimum
Default
Maximum
40°F
5°C
120°F
49°C
200°F
93°C
Force Screens
Refer to the following map when navigating through the Force
Screens. From the FORCE Screen, press
<ENTER>
.
FORCE
VALVES
FORCE
MODE ON/OFF
FRC VALV
X%
FORCE VALVE PERCENTAGE
This screen only appears when Force Mode is on.
This screen will appear when the Force Mode times out after 1 hour.
FORCE
TIMEOUT
Press the
<UP> button to turn the Force Mode on.
Press the
<DOWN> button to turn the Force Mode off.
Press the
<UP> button to increase the percentage.
Press the
<DOWN> button to decrease the percentage.
NOTE: When you turn the Force Mode back off or after
1 hour has elapsed, the valve will reinitialize to zero.
FORCE MODE TIME OUT
STAGE 1
MODULATING
STAGE 2-14
FORCE ON OR OFF
The next 15 screens are for Relays Only.
Press the
<UP> button to turn the Force the Relay on.
Press the
<DOWN> button to turn the Force the Relay off.
This Relay cannot be forced.