Lcd display screens, Setpoint & force screens, Modgas-x field technical guide 18 – Orion System MODGAS-X User Manual

Page 18: Setpoint screens, Force screens

Advertising
background image

LCD DISPLAY SCREENS

MODGAS-X Field Technical Guide

18

Setpoint & Force Screens

Setpoint Screens

Refer to the following map when navigating through the Set-
point Screens. From the SETPOINTS Screen, press

<ENTER>

to scroll through the screens and change setpoints. Use the

<UP>

and

<DOWN>

arrow keys to change your selections. Then press

<ENTER>

to save the new setpoint.

NOTE: When the MODGAS-X is operating in

Communications Mode, these setpoint screens
will not appear on the LCD display because
they are controlled by the Main Controller.

SETPOINTS

SAT SP

40-200°F

5-93°C

RESET SP

40-200°F

5-93°C

HEATING SUPPLY AIR TEMPERATURE SETPOINT

This is the target temperature while the heating is enabled. If you are
using the reset signal, this is the setpoint it will calculate to at zero volts.
Will display only in stand-alone mode.

The SAT Setpoint is set by the LCD Display in stand-alone mode and is
set by the Main Controller in communicating mode.

Minimum

Default

Maximum

40°F

5°C

120°F

49°C

200°F

93°C

RESET HEATING SUPPLY AIR SETPOINT

This is the maximum temperature at which the Supply Air Temperature
will reset to. Will display only in stand-alone mode.

The Reset Setpoint is set by the LCD Display in stand-alone mode and
is set by the Main Controller in communicating mode.

Minimum

Default

Maximum

40°F

5°C

120°F

49°C

200°F

93°C

Force Screens

Refer to the following map when navigating through the Force
Screens. From the FORCE Screen, press

<ENTER>

.

FORCE

VALVES

FORCE

MODE ON/OFF

FRC VALV

X%

FORCE VALVE PERCENTAGE

This screen only appears when Force Mode is on.

This screen will appear when the Force Mode times out after 1 hour.

FORCE

TIMEOUT

Press the

<UP> button to turn the Force Mode on.

Press the

<DOWN> button to turn the Force Mode off.

Press the

<UP> button to increase the percentage.

Press the

<DOWN> button to decrease the percentage.

NOTE: When you turn the Force Mode back off or after

1 hour has elapsed, the valve will reinitialize to zero.

FORCE MODE TIME OUT

STAGE 1

MODULATING

STAGE 2-14

FORCE ON OR OFF

The next 15 screens are for Relays Only.

Press the

<UP> button to turn the Force the Relay on.

Press the

<DOWN> button to turn the Force the Relay off.

This Relay cannot be forced.