MODGAS-X Field Technical Guide

LCD DISPLAY SCREENS

17

Status & Alarm Screens

Status Screens

Refer to the following map when navigating through the Status
Screens. From the STATUS Screen, press

<ENTER>

to scroll

through the screens.

STATUS

MODE
HEAT

VLV POS

100%

SA TEMP

XX.X

ACTIV SP

XX.X

Alarm Screens

Refer to the following map when viewing Alarm Screens. These
screens will display automatically when alarms are present. For
alarm troubleshooting, see pages 19 & 20.

SUPPLY AIR TEMPERATURE

40ºF to 200ºF or 5ºC to 93ºC.

If no sensor is detected, screen will display “NO SENSR”

ALARMS

Status Screens shown below will scroll automatically if LCD display is
left on this screen for 20 seconds.

MODE

This screen displays the current mode of operation of the MODGAS-X
Controller. The mode options are:

OFF:

This mode will display when there is no call for heat and heating

has been disabled.

HIGH FIRE:

Each time Heat is activated, the unit will fi rst go into High

Fire Mode. During this mode, the unit will remain at maximum fi re. The
unit will leave this mode once proof of fi re has been established.

HEAT:

After High Fire, the unit will enter the Heat Mode and will begin

to modulate the gas valve to maintain the Heating Supply Air Setpoint
(SAT). The unit must remain in this mode for a minimum run time of 1
minute. While in Heat Mode, the screen will display the staging status—
HEAT STAGE 1 to STAGE 16. If Modulating Staged Heat, the screen will
display MOD HEAT. Once the call for heat goes away, the unit will leave
the Heat Mode.

CUTOFF:

The Cutoff Mode occurs if the SAT rises above 200˚F. During

Cutoff Mode, the Heat will be disabled for a fi xed delay period. If the SAT
falls below 200˚F and the delay period has expired, the unit will re-enter
the Heat Mode.

FORCE:

Force Mode.

SAT FAIL:

The Supply Air Temperature sensor has been disconnected

for more than 60 seconds. This alarm will be disabled when the sensor
is reconnected.

VALVE POSITION

0 to 100 percent

ACTIVE SUPPLY AIR SETPOINT

Calculated from SAT setpoint and reset signal in stand-alone mode. In

communicating mode, the Main Controller sends the setpoint.

ALARMS

The alarms are as follows:

NO ALARMS:

This will be shown if there are no current alarms.

SAT CUTOFF:

This indicates a Supply Air Temperature Cutoff Alarm

condition which is activated if the SAT has risen above 200ºF. The alarm
will go away if after a fi xed delay period the SAT has dropped below
200ºF.

MECH FAILURE:

The unit has been in High Fire Mode for more time

than the mechanical failure delay period. This alarm will be disabled
when the unit leaves High Fire Mode.

SAT FAIL ERROR:

The Supply Air Temperature sensor has been dis-

connected for more than 60 seconds. This alarm will be disabled when
the sensor is reconnected.

COMM T/O ERROR:

Communications have been lost with the main

controller. This alarm will disable when communications resume.

FAN SPD

OFF,HIGH,LOW

FAN SPEED

OFF, HIGH, LOW