Wiring, Modgas-x field technical guide 6 – Orion System MODGAS-X User Manual

Page 6

Advertising
background image

WIRING

MODGAS-X Field Technical Guide

6

Single Modulating Valve No Staging - Communicating Wiring

Figure 3: Single Modulating Valve No Staging Communicating Wiring Diagram

MODGAS-X CONTROLLER

(OE377-26-00058)

Supply

Air Temperature

Sensor

Mount In Supply

Air Duct

Connect

o AI2 & GND

On Main Controller

(This Does Not Apply To

Retrofit Applications.

See

.)

Supply Air Temperature

Sensor T

Table 7, Page 24

EBC E-BUS Cable

Connects To

VCB-X Controller’s

Expansion

Port

Low Speed Fan

24 VAC Power
Input Terminals
Max. Power
Consumption
1 Gas Valve
= 18 VA
2 Gas Valves
= 33 VA

I C Cable

Connects To

I C Port On

Any Non VCB-X Controller

Or Expansion Module

2

2

Fan Enable And

Stage 1 Heat (Mod)

The SAT OPTIONS Jumper Setting

Should Be Set to 1.

See

For Settings.

Only One Supply Air Temperature Sensor

Can Be Used Per Application.

Table 9, Page 24

Single Modulating Valve No Staging -

Communicating Wiring

This confi guration operates as Stand-Alone (Figure 2, page 5) or
communicating with an AAON Unit Controller (Figure 3, below).

For connection to a VCB-X Controller or VCB-X Expansion Mod-
ule, use an E-BUS Cable connecting to the appropriate E-BUS ports
on those controllers. For all other controllers, including VAV/CAV,
MUA, VCM, VCM-X, SA, and RNE Controllers, use an I

2

C Cable

connecting to the appropriate I

2

C ports on those controllers.

This confi guration

can use either the MAXITROL

®

0-20 volt valve(s)

or the MAXITROL

®

EXA STAR 0-10 volt stepper valve(s)—confi g-

ured at the factory.

See Appendix C, page 26 for depiction.

WARNING: Do Not Connect Power To VOUT/Ground

Terminal

Block!

NOTE: If additional fi xed stages are required, these should be

confi gured and wired to the AAON Unit Controller’s
relays.

Advertising