Wiring, Modgas-x field technical guide – Orion System MODGAS-X User Manual

Page 7

Advertising
background image

MODGAS-X Field Technical Guide

WIRING

7

Single Modulating Valve & Up To 14 Stages Fixed Heat Stand-Alone

Figure 4: Single Modulating Valve - Stand-Alone

MODGAS-X CONTROLLER

(OE377-26-00058)

See

For

Settings.

Only One Supply Air Temperature Sensor

Can Be Used Per Application.

Table 8, Page 24

SAT OPTIONS Jumper

24 VAC Power
Input Terminals
Max. Power
Consumption
1 Gas Valve
= 18 VA

EBC-E-BUS Cable

Connects To

12 Relay E-BUS

Expansion

Port

Fan Enable And

Stage 1 Heat (Mod)

Low Speed Fan

Stage 2 Heat (Fixed)

Stage 3 Heat (Fixed)

3

Connect SAT and

Input to

Board’s

Input If

Applicable.
See

.

GND
Reheat
SAT

Table 7,

Page 24

One Modulating Valve With Up To 14

Additional Stages Of Fixed Heat

Stand-Alone Wiring

This confi guration only applies to a Stand-Alone operation (Figure
4, below
) and is factory-confi gured.

If using a MHGRV-X Controller along with the MODGAS-X
Controller in Stand-Alone, the SAT Sensor always connects to the
MODGAS-X Controller.

The fi rst two fi xed stages use AUX1 and AUX2 relays to enable
them (Figure 4, below). Additional fi xed stages can be added by
using the 12-Relay E-BUS Expansion Module. (Figure 5, page 8).

This configuration

can use either the MAXITROL

®

0-20 volt

valve(s) or the MAXITROL

®

EXA STAR 0-10 volt stepper valve(s)

(confi gured at the factory).

See Appendix C, page 26 for depiction.

WARNING: Do Not Connect Power To VOUT/Ground

Terminal

Block!

Advertising