MODGAS-X Field Technical Guide

WIRING

9

Two Modulating Valves & Up To 13 Stages Fixed Heat Stand-Alone

Figure 6: Two Modulating Valves - Stand-Alone

MODGAS-X CONTROLLER

(OE377-26-00058)

See

For

Settings.

Only One Supply Air Temperature Sensor

Can Be Used Per Application.

Table 8, Page 24

SAT OPTIONS Jumper

EBC-E-BUS Cable

Connects To

12 Relay E-BUS

Expansion

Port

Fan Enable And

Stage 1 Heat (Mod)

Low Speed Fan

Stage 2 Heat (Mod)

Stage 3 Heat (Fixed)

3

Connect SAT and

Input to

Board’s

Input If

Applicable.
See

.

GND
Reheat
SAT

Table 7,

Page 24

24 VAC Power
Input Terminals
Max. Power
Consumption
1 Gas Valve
= 18 VA
2 Gas Valves
= 33 VA

Two Modulating Valves With Up To 13

Additional Stages Of Fixed Heat

Stand-Alone Wiring

This confi guration only applies to a Stand-Alone operation (Figure
6, below
) and is factory-confi gured.

In this confi guration, the fi rst Modulating Valve is enabled by the
FAN RLY. The second Modulating Valve is enabled by the AUX1
relay. The fi xed stage uses the AUX2 relay to enable it (Figure 6,
below)
. Additional fi xed stages can be added by using the 12-Relay
E-BUS Expansion Module. (Figure 7, page 10).

If using a MHGRV-X Controller along with the MODGAS-X
Controller in Stand-Alone, the SAT Sensor always connects to the
MODGAS-X Controller.

This configuration

can use either the MAXITROL

®

0-20 volt

valve(s) or the MAXITROL

®

EXA STAR 0-10 volt stepper valve(s)

(confi gured at the factory).

See Appendix C, page 26 for depiction.

WARNING: Do Not Connect Power To VOUT/Ground

Terminal

Block!