WIRING

MODGAS-X Field Technical Guide

12

Two Modulating Staged Valves - Communicating Wiring

Two Modulating Staged Valves -

Communicating Wiring

This confi guration operates as Stand-Alone (Figure 8, page 11) or
communicating with an AAON Unit Controller (Figure 9, below).

For connection to a VCB-X Controller or VCB-X Expansion Module,
use an E-BUS Cable connecting to the appropriate E-BUS ports on
those controllers.

For all other controllers, including VAV/CAV, MUA, VCM, VCM-
X, SA, and RNE Controllers, use an I

2

C Cable connecting to the

appropriate I

2

C ports on those controllers.

If using the VCM-X Controller (I

2

C), extra fi xed stages can be added

by using the VCM-X Expansion Module.

This configuration

can use either the MAXITROL

®

0-20 volt

valve(s) or the MAXITROL

®

EXA STAR 0-10 volt stepper valve(s)

(confi gured at the factory).

See Appendix C, page 26 for depiction.

WARNING: Do Not Connect Power To VOUT/Ground

Terminal

Block!

Figure 9: Two Modulating Staged Valves Communicating Wiring Diagram

MODGAS-X CONTROLLER

(OE377-26-00058)

Supply

Air Temperature

Sensor

Mount In Supply

Air Duct

EBC E-BUS Cable

Connects To

VCB-X Controller’s

Expansion

Port

Low Speed Fan

24 VAC Power
Input Terminals
Max. Power
Consumption
1 Gas Valve
= 18 VA
2 Gas Valves
= 33 VA

Stage 2 Heat (Mod)

I C Cable

Connects To

VCM-X Controller’s

Expansion

Port

2

Fan Enable and

Stage 1 Heat (Mod)

The SAT OPTIONS Jumper Setting

Should Be Set to 1.

See

For Settings.

Only One Supply Air Temperature Sensor

Can Be Used Per Application.

Table 9, Page 24

Connect

o AI2 & GND

On Main Controller

(This Does Not Apply To

Retrofit Applications.

See

.)

Supply Air Temperature

Sensor T

Table 7, Page 24