Sequence of operations, Operation modes – Orion System PREHEAT-X User Manual

Page 10

Advertising
background image

Zone

Zone

SEQUENCE OF OPERATIONS

10

PREHEAT-X Technical Guide

Preheat Enable

Stand Alone Mode

Enabled when the Binary Input is closed and the Entering Air Tem-
perature is below setpoint.

E-BUS Communications Mode

Enabled by an E-BUS command when the Entering Air Temperature
falls below the Preheat Setpoint.

BACnet Communications Mode

Enabled by BACnet command or Binary Input, whichever occurs
fi rst.

Leaving Air Sensor

The controller can be confi gured to use one of three sensor confi gu-
rations for control.

Leaving Air Sensor 1 only (LAT1)

Leaving Air Sensor 2 only (LAT2)

Average Leaving Air Temperature which averages

LAT1 and LAT2

Leaving Air Setpoint

Stand Alone

Leaving Air Temperature Setpoint can be reset

between the LAT Setpoint and LAT Setpoint Reset

Limit.

The Reset Source is based on a 0-10 VDC input and

range can be adjusted using the LAT Setpoint Reset

Source Low and LAT Setpoint Reset Source High

Setpoints.

E-BUS and BACnet Communications Mode

A Leaving Air Temperature Setpoint will be sent to

the

controller.

This value is stored in volatile memory and will be

lost at reset.

There are separate Leaving Air Temperature Setpoints,

depending on if the unit is in Heating, Vent, or Cool

Mode.

Modulating Heat

• If

confi gured, the Modulating Heat output will be used

as

the

fi rst stage of heat.

Analog Voltage Output can be adjusted between

0-10 VDC as needed to maintain the Leaving Air

Setpoint.

Controlled by an Internal PID Loop.

Heat Staging Up

The following conditions must be met before the fi rst (next) stage
of heat can be energized:

Preheat Enable Signal/Command must be active.

The LAT must be below the LAT Setpoint by any

amount.

If Mod Heat is confi gured, it must be at 100% for the

Stage Up Delay.

The Minimum Off Time must be met.

The Stage Up Delay must be met (for second stage

and

above).

Heat Staging Down

The following conditions must be met before a stage of heat can be
de-energized:

Preheat Enable Signal/Command is deactivated

-OR- the LAT must be above the LAT Setpoint by the

LAT

Deadband.

If Modulating Heat is confi gured, it must be at 0% for

the stage down delay.

The Minimum Run time must be met.

The Stage Down Time must be met.

Operation Modes