APPENDIX B

25

PREHEAT-X BACnet

®

Connection To MS/TP Network

Figure 8: PREHEAT-X BACnet Connection to MS/TP Network

MS/TP Connection

To BACnet

®

SHLD

T -

R +

Typical Terminal Blocks. All
Wiring To Be T To T, SHLD
(G) To SHLD (G) & R To R

Wiring Notes:
1.) All wiring to be in accordance with local and national electrical
codes and specifications.

2.) All communication wiring to be 18 gauge minimum, 2 conductor
twisted pair with shield. Use Belden #82760 or equivalent.

24VAC

GND

Line Voltage

Size Transformer For
Correct Total Load.
PREHEAT-X Controller =
40 VA

PREHEAT-X

CONTROLLER

Programming Note:

See Page 20

Use Communication
Configuration Screens In
LCD Display To Program
The BACnet Settings.

For Details.

M

ENTER

UP

DOWN

ALARM

MENU

ALARM CONTACT

HEAT 1

HEAT 2

HEAT 3

HEAT 4

HEAT 5

HEAT 6

RLY COMM

HEAT

OUTPUTS

ANALOG

OUTPUTS

0-10V MOD. SCR

GND

PWM +

PWM -

OE377-26-00061 PREHEAT-X

AAON No.: V48510

WattMaster Label

#LB102XXX-A

Rev.: 1A

E-BUS

CONNECT

E-BUS

CONNECT

LAT1

0-10V RESET

LAT2

OAT

GND

GND

ANALOG INPUTS

BINARY INPUTS

RS-485 COMM

+2

4

V

AC

GND

www.orioncontrols.com

www.aaon.com

ENABLE

T(-)

EMERG. SHUTDOWN

SHLD

FUTURE USE

R(+)

CONTACT RATING IS

1 AMP MAX

@ 24 VAC

M

ENTER

UP

DOWN

ALARM

MENU

ALARM CONTACT

HEAT 1

HEAT 2

HEAT 3

HEAT 4

HEAT 5

HEAT 6

RLY COMM

HEAT

OUTPUTS

ANALOG

OUTPUTS

0-10V MOD. SCR

GND

PWM +

PWM -

OE377-26-00061 PREHEAT-X

AAON No.: V48510

WattMaster Label

Rev.: 1B

#S

000062

W

E-BUS

CONNECT

E-BUS

CONNECT

LAT1

0-10V RESET

LAT2

OAT

GND

GND

ANALOG INPUTS

BINARY INPUTS

RS-485 COMM

+24 V

A

C

GND

www.aaon.com

ENABLE

T(-)

EMERG. SHUTDOWN

SHLD

FUTURE USE

R(+)

CONTACT RATING IS

1 AMP MAX

@ 24 VAC

www.orioncontrols.com

MSTP

BACnet

M

ENTER

UP

DOWN

ALARM

MENU

ALARM CONTACT

HEAT 1

HEAT 2

HEAT 3

HEAT 4

HEAT 5

HEAT 6

RLY COMM

HEAT

OUTPUTS

ANALOG

OUTPUTS

0-10V MOD. SCR

GND

PWM +

PWM -

OE377-26-00061 PREHEAT-X

AAON No.: V48510

WattMaster Label

Rev.: 1D

#S

000062

W

E-BUS

CONNECT

E-BUS

CONNECT

LAT1

0-10V RESET

LAT2

EAT

GND

GND

ANALOG INPUTS

BINARY INPUTS

RS-485 COMM

+24 V

A

C

GND

www.aaon.com

ENABLE

T(-)

EMERG. SHUTDOWN

SHLD

FUTURE USE

R(+)

CONTACT RATING IS

1 AMP MAX

@ 24 VAC

www.orioncontrols.com

MSTP

BACnet

Advertising