TROUBLESHOOTING

PREHEAT-X Technical Guide

24

LAT Sensor Testing

Leaving Air Temperature Sensor

If you suspect the Leaving Air Temperature Sensor is not reading
correctly, make sure the wiring terminal connections are tight and
that any wiring splices are properly connected. You can check the
operation of the Leaving Air Temperature Sensor by measuring
the resistance or voltage using a digital multimeter. Set the meter
to DC Volts. Place the positive probe on the AIN terminal and the
negative probe on the GND terminal. Read the DC Volts and fi nd
that voltage in Table 3.

Read the temperature corresponding with that voltage and determine
if this is close to the actual temperature the sensor is exposed to. If the
temperature from the chart is different by more than a few degrees,
you probably have a defective or damaged sensor. You can also
check the sensor resistance to determine correct operation. To read
the resistance, set the meter to Ohms. Unplug the sensor connector
from the board and measure the resistance across the disconnected
wires. This resistance should match the corresponding temperature
from Table 3.

Temperature to Resistance/Voltage Chart

Temp

(

°F)

Temp

(

°C)

Resistance

(Ohms)

Voltage @

Input (VDC)

-10

-23.3

93333

2.98

-5

-20.6

80531

2.94

0

-17.8

69822

2.89

5

-15.0

60552

2.83

10

-12.2

52500

2.77

15

-9.4

45902

2.71

20

-6.7

40147

2.64

25

-3.9

35165

2.57

30

-1.1

30805

2.49

35

1.6

27140

2.41

40

4.4

23874

2.33

45

7.2

21094

2.24

50

10.0

18655

2.15

52

11.1

17799

2.11

54

12.2

16956

2.08

56

13.3

16164

2.04

58

14.4

15385

2.00

60

15.6

14681

1.96

62

16.7

14014

1.93

64

17.8

13382

1.89

66

18.9

12758

1.85

Temperature to Resistance/Voltage Chart

Temp

(

°F)

Temp

(

°C)

Resistance

(Ohms)

Voltage @

Input (VDC)

68

20.0

12191

1.81

69

20.6

11906

1.79

70

21.1

11652

1.78

71

21.7

11379

1.76

72

22.2

11136

1.74

73

22.7

10878

1.72

74

23.3

10625

1.70

75

23.9

10398

1.68

76

24.4

10158

1.66

78

25.6

9711

1.63

80

27.8

9302

1.59

82

27.8

8893

1.55

84

28.9

8514

1.52

86

30.0

8153

1.48

88

31.1

7805

1.45

90

32.2

7472

1.41

95

35.0

6716

1.33

100

37.8

6047

1.24

105

40.6

5453

1.16

110

43.3

4923

1.09

115

46.1

4449

1.02

120

48.9

4030

.95

125

51.7

3656

.88

130

54.4

3317

.82

135

57.2

3015

.76

140

60.0

2743

.71

145

62.8

2502

.66

Table 3: 0-3.3 V Temperature Sensor - Voltage &
Resistance for Type III Sensors

Table 3, continued: 0-3.3 V Temperature Sensor -
Voltage & Resistance for Type III Sensors

Thermistor Sensor Testing Instructions

1.) Use the resistance column to check the thermistor sensor while
disconnected from the controllers (not powered).

2.) Use the voltage column to check sensors while connected to
powered controllers. Read voltage with meter set on DC volts. Place
the “-” (minus) lead on GND terminal and the “+” (plus) lead on the
sensor input terminal being investigated.

If the voltage is above 3.3 VDC, the sensor or wiring is “open.” If
the voltage is less than 0.05 VDC, the sensor or wiring is shorted.