Appendix b, Preheat-x bacnet, Points – Orion System PREHEAT-X User Manual

Page 26: Preheat-x technical guide 26, Property identifi er

Advertising
background image

APPENDIX B

PREHEAT-X Technical Guide

26

PREHEAT-X BACnet

®

Points

BACnet

®

Properties for the PREHEAT-X

PARAMETER

OBJECT

DESCRIPTION

LIMITS

Active

Controlling

Setpoint

AI: 1

The current Active

Controlling Setpoint

Read Only

Number of

Heat Stages

On

AI:2

The current number of heat

stages on

Read Only

Modulating

Output

Position

AI: 3

The current Modulating

Output Position

Read Only

All Alarms

Bitfi eld

AI: 4

The current Alarm Status

in a Bitfi eld

Read Only

See Alarm

Bits, this page.

Entering Air

Temperature

AI: 5

The current Entering Air

Temperature

Read Only

Leaving Air

Temp Sensor 1

AI:6

The current Leaving Air

Sensor 1 Temperature

Read Only

Leaving Air

Temp Sensor 2

AI:7

The current Leaving Air

Sensor 2 Temperature

Read Only

Leaving Air

Average Temp

AI: 8

The current Average

Leaving Air Temperature

Read Only

Reset Input

Percentage

AI:9

The current Setpoint Reset

Input Percentage

Read Only

Enable Input

Value

BI: 1

The current value of the

Enable Binary Input

Read Only

0 = Off

1 = On

Shutdown

Input Value

BI: 2

The current value of the

Emergency Shutdown

Binary Input

Read Only

0 = Off

1 = On

Preheat Enable

Status

BI: 3

The current Enable status

of the controller

Read Only

0 = Off

1 = On

Alarm Relay

Status

BI: 4

The current status of the

Alarm Relay

Read Only

0 = Off

1 = On

Heat 1 Relay

Status

BI: 5

The current status of the

Heat 1 Relay

Read Only

0 = Off

1 = On

Heat 2 Relay

Status

BI: 6

The current status of the

Heat 2 Relay

Read Only

0 = Off

1 = On

Heat 3 Relay

Status

BI: 7

The current status of the

Heat 3 Relay

Read Only

0 = Off

1 = On

Heat 4 Relay

Status

BI: 8

The current status of the

Heat 4 Relay

Read Only

0 = Off

1 = On

Heat 5 Relay

Status

BI: 9

The current status of the

Heat 5 Relay

Read Only

0 = Off

1 = On

Heat 6 Relay

Status

BI: 10

The current status of the

Heat 6 Relay

Read Only

0 = Off

1 = On

BACnet

®

Properties for the PREHEAT-X

PARAMETER

OBJECT

DESCRIPTION

LIMITS

Emergency

Shutdown

Alarm

BI: 11

The current Emergency

Shutdown Alarm status

Read Only

0 = Off

1 = On

Leaving Air

Sensor 1

Alarm

BI: 12

The current Leaving Air

Sensor 1 Alarm status

Read Only

0 = Off

1 = On

Leaving Air

Sensor 2

Alarm

BI: 13

The current Leaving Air

Sensor 2 Alarm status

Read Only

0 = Off

1 = On

Low Leaving

Air Temp

Alarm

BI: 14

The current Low Leaving

Air Temp Alarm status

Read Only

0 = Off

1 = On

High Leaving

Air Temp

Alarm

BI: 15

The current High Leaving

Air Temp Alarm status

Read Only

0 = Off

1 = On

Entering Air

Sensor Alarm

BI: 16

The current Entering Air

Sensor Alarm status

Read Only

0 = Off

1 = On

Remote Enable

AV: 1

Enables the Preheat from

the BACnet front end

Read / Write

Volatile

0 = Disabled

1 = Enabled

Remote

Leaving Air

Setpoint

AV: 2

Controlling Leaving Air

Setpoint from the BACnet

front end

Read/ Write

Volatile

35.0 ºF

90.0

ºF

Remote

Entering

Air Enable

Setpoint

AV: 3

Entering Air Enable

Setpoint from the BACnet

Front end

Read / Write

Volatile

-40.0

ºF

90.0

ºF

PREHEAT-X BACnet

®

Property

Identifi er

BACNETPropertyIdentifi er :

AllAlarmGroup1Bits ::= BIT STRING {

Reserved

(0),

BadLeavingAir1

(1),

BadLeavingAir2

(2),

LowLeavingAir

(3),

HighLeavingAir

(4),

Reserved

(5),

BadEnteringAir (6),
CommAlarm

(7),

ShutDownAlarm

(8)