Lcd display screens, Setpoint & alarm screens, Preheat-x technical guide – Orion System PREHEAT-X User Manual

Page 17: 17 alarm screens

Advertising
background image

PREHEAT-X Technical Guide

LCD DISPLAY SCREENS

17

Alarm Screens

Refer to the following map when viewing Alarm Screens. These
screens will display automatically when alarms are present. For
alarm troubleshooting, see pages 21-22.

ALARMS

ALARMS

The alarms are as follows:

NO ALARMS:

This will be shown if there are no current alarms.

E-SHDN:

If 24VAC is removed from the Emergency Shutdown Input,

this alarm will activate and the controller will turn off all outputs. The
alarm will be disabled when voltage has returned.

LA1 SENS:

The fi rst Leaving Air Temperature Sensor has been discon-

nected, shorted, open, or missing for more than 60 seconds. This alarm
will be disabled when the sensor is working again.

LA2 SENS:

The second Leaving Air Temperature Sensor has been

disconnected, shorted, open, or missing for more than 60 seconds. This
alarm will be disabled when the sensor is working again.

LO LAT:

This indicates a Leaving Air Temperature Cutoff Alarm condi-

tion which is activated if the Controlling Leaving Air Temperature has
dropped below 35ºF for more than 2 minutes. The alarm will be disabled
if after a fi xed delay period the Leaving Air Temperature has risen above
35ºF.

HI LAT:

This indicates a Leaving Air Temperature Cutoff Alarm condition

which is activated if the Controlling Leaving Air Temperature has risen
above 120ºF. All outputs will stage off.

EA SENS:

The Entering Air Temperature Sensor has been disconnect-

ed, open, shorted, or missing for more than 60 seconds. This alarm will
be disabled when the sensor is working again.

COM STAT:

Communications have been lost with the main controller

for more than 30 seconds. This alarm will disable when communications
resume.

Setpoint & Alarm Screens

EA CAL

XX.X°F

XX.X°C

ENTERING AIR SENSOR CALIBRATION OFFSET

If the sensor is reading incorrectly, you can use this screen to enter an
offset temperature to adjust the sensor’s temperature. Enter a positive
value to raise the sensor’s temperature or a negative value to lower the
sensor’s temperature.

Minimum

Default

Maximum

-100.0°F

-55.5°C

0.0°F

0.0°C

100.0°F

55.5°C

Advertising