SEQUENCE OF OPERATIONS

11

PREHEAT-X Technical Guide

Emergency Shutdown

The Emergency Shutdown input must always be used and wired
as a 24 VAC normally closed contact. If an Emergency Shutdown
occurs, and that contact opens:

All outputs will be immediately de-energized.

An alarm will be generated.

High Leaving Air Temperature Alarm

If the Leaving Air Temperature is above the LAT High

Temperature Alarm Limit for more than the Alarm

Delay all heating outputs will be de-energized

immediately.

An alarm will be generated.

A manual reset will be required.

Low Leaving Air Temperature Alarm

If the Leaving Air Temperature is below the LAT Low Temperature
Alarm Limit for more than 2 minutes, the heat will remain on but
an alarm will be generated.