SEQUENCE OF OPERATIONS

11

PREHEAT-X Technical Guide

Emergency Shutdown

The Emergency Shutdown input must always be used and wired
as a 24 VAC normally closed contact. If an Emergency Shutdown
occurs, and that contact opens:

•

All outputs will be immediately de-energized.

•

An alarm will be generated.

High Leaving Air Temperature Alarm

•

If the Leaving Air Temperature is above the LAT High

Temperature Alarm Limit for more than the Alarm

Delay all heating outputs will be de-energized

immediately.

•

An alarm will be generated.

•

A manual reset will be required.

Low Leaving Air Temperature Alarm

If the Leaving Air Temperature is below the LAT Low Temperature
Alarm Limit for more than 2 minutes, the heat will remain on but
an alarm will be generated.

Operation Modes