PREHEAT-X Technical Guide

APPENDIX A

23

Leaving Air Temperature Sensor Installation

Mounting the Leaving Air Temperature

Sensor

The Leaving Air Temperature (LAT) Sensor should be

located in PREHEAT-X box’s output location.

Locate the sensor in the center of the widest part of the

PREHEAT-X box wall. Use the supplied template and a

5/16” drill to make a hole for the sensor.

Install the gasket over the probe and mount securely to

the box wall using the supplied sheet metal screws. Be sure

the gasket is compressed to provide an air tight seal.

For best accuracy, apply insulation on the outside of the

box wall, over the sensor. This will help prevent thermal

gradients from affecting the sensor.

Figure 7: Leaving Air Temperature Sensor Installation

Leads Are Non-Polarized. Butt Splice Leads
To 24 Gauge Wire Minimum.

Connect Leads to ”AIN1 And/Or “AIN2” And “GND” On
PREHEAT-X Controller. See Figure 2 on page 5 for
details.

Inside Wall of PREHEAT-X Box

WARNING: Make sure your Leaving Air Temperature

Sensor(s) are mounted and wired according

to these instructions prior to testing the unit

or else the modulating valve will not control

properly and may damage your equipment.