SCALING

DEG. F

DEG. C

TEMPERATURE SCALE

Fahrenheit (default) or Celsius.

This setting is used only in stand-alone mode.

STG UP

0-1200 SECONDS

STAGE UP DELAY

If confi gured for SCR modulation, this is the amount of time (in sec-

onds) the controller must wait to activate an additional stage of heat if

the Min Off Time is met. Range is 0 - 1200. Default is 180.

STG DWN

0-1200 SECONDS

STAGE DOWN DELAY

If confi gured for SCR modulation, This is the amount of time (in sec-

onds)the controller must wait to deactivate a stage of heat if the Min

Run time is met. Range is 0 - 1200. Default is 180.

MIN RUN

0-1200 SECONDS

MINIMUM RUN TIME

This is the amount of time (in seconds) a stage of heat must remain on

before it can be deactivated. Range is 0 - 1200. Default is 120.

MIN OFF

0-1200 SECONDS

MINIMUM OFF TIME

This is the amount of time (in seconds) a stage of heat must remain off

before it can be activated. Range is 0 - 1200. Default is 60.