LCD DISPLAY SCREENS

PREHEAT-X Technical Guide

16

Setpoint Screens

Refer to the following map when navigating through the Set-
point Screens. From the SETPOINTS Screen, press

<ENTER>

to scroll through the screens and change setpoints. Use the

<UP>

and

<DOWN>

arrow keys to change your selections. Then press

<ENTER>

to save the new setpoint.

NOTE: When the PREHEAT-X is operating in

Communications Mode, these setpoint screens
will not appear on the LCD display because
they are controlled by the Main Controller.

SET

POINTS

LA SP

XX.X°F

XX.X°C

RST LMT

XX.X°F

XX.X°C

LEAVING AIR TEMPERATURE SETPOINT

Will display only in stand-alone mode. This is the target temperature
while the heating is enabled. If you are using the reset signal, this is the
setpoint it will calculate to at zero volts.

The LA Setpoint is set by the LCD Display in stand-alone mode and is
set by the Main Controller in communicating mode.

Minimum

Default

Maximum

35°F

1.6°C

70°F

21°C

90°F

32°C

RESET LIMIT SETPOINT

Will display and be used only in stand-alone mode. If Remote Reset is
being utilized, this will be the Leaving Air Setpoint when the Reset Volt-
age Input is at 10VDC.

Minimum

Default

Maximum

0°F

°C

70°F

°C

120°F

°C

Setpoint Screens

EA EN SP

XX.X°F

XX.X°C

ENTERING AIR ENABLE SETPOINT

This is the temperature at which Preheat is enabled. The Entering Air
Enable Setpoint is set by the LCD Display in stand-alone mode and is
set by the Main Controller in communicating mode.

Minimum

Default

Maximum

-40°F

-40°C

55°F

12.7°C

90°F

32°C

LA1 CAL

XX.X°F

XX.X°C

LEAVING AIR SENSOR 1 CALIBRATION OFFSET

If the sensor is reading incorrectly, you can use this screen to enter an
offset temperature to adjust the sensor’s temperature. Enter a positive
value to raise the sensor’s temperature or a negative value to lower the
sensor’s temperature.

Minimum

Default

Maximum

-100.0°F

-55.5°C

0.0°F

0.0°C

100.0°F

55.5°C

LA2 CAL

XX.X°F

XX.X°C

LEAVING AIR SENSOR 2 CALIBRATION OFFSET

If the sensor is reading incorrectly, you can use this screen to enter an
offset temperature to adjust the sensor’s temperature. Enter a positive
value to raise the sensor’s temperature or a negative value to lower the
sensor’s temperature.

Minimum

Default

Maximum

-100.0°F

-55.5°C

0.0°F

0.0°C

100.0°F

55.5°C