Recovering from a failed K2 Media Server system battery
When the system battery in a K2 Media Server fails (non rechargeable) the system
configuration is lost, and the system will not complete startup processes when the
battery is replaced.
To recover from a failed battery, do the following:
1. Restart the K2 Media Server.
A startup screen displays the message “Invalid configuration information - Please
run setup program. Time of day not set - Please run setup program.”
2. Press
F2
to enter setup.
3. Set the system date and time
4. Select
System Setup | Integrated Devices
5. Select
RAID
. This also sets ChA and ChB to RAID
6. Restart the K2 Media Server.
A startup screen displays the message “Warning: Detected mode change from
SCSI to RAID on ChA of the embedded RAID system.”
7. Select
Yes
.
A startup screen displays the message “Warning: Detected mode change from
SCSI to RAID on ChB of the embedded RAID system.”
8. Select
Yes
.
The K2 Media Server restarts as normal.
When startup completes, normal operation is restored.