5 Installation Procedure
YASKAWA ELECTRIC
SIEP C730600 44A YASKAWA AC Drive-Option Card CC-Link Technical Manual
15
Figure 8
Figure 8 Cable Diagram
■
Terminal Resistor Connection
When the CC-Link Option is the last station connected in a CC-Link network, the terminal resistor needs to be set to that CC-Link Option. Follow
the instructions below.
1.
Cut the terminal resistor tube as shown.
Note: For the terminal resistor, either use what is already built into the master unit, or use a standard-market resistor of 110
Ω, ±5% (1/2 W).
Figure 9
Figure 9 Terminal Resistor
2.
Loosen the attachment screw and insert the terminal resistor described in the first step between terminals DA and DB.
Figure 10
Figure 10 Terminal Resistor Wiring
A – sheath
F – drain (concentrated)
B – shield
G – DB
C – aluminum tape
H – DA
D – DG
I – drain (spread out)
E – ground
A
B
C
D
E
H
G
F
white
blue
yellow
A
B
C
D
E
H
G
I
white
blue
yellow
jumper
cut here
cut
DA DB DG SLD SLD