9 troubleshooting – Yaskawa 1000 Series Drive Option - CC-Link Technical Manual User Manual

Page 25

Advertising
background image

9 Troubleshooting

YASKAWA ELECTRIC

SIEP C730600 44A YASKAWA AC Drive-Option Card CC-Link Technical Manual

25

Faults when running multiple drives

The example below demonstrates how to read the LED display on the front cover of the drive to determine the cause of a fault and the corrective

action to take when multiple drives are running from the same network. The example assumes that SW, M/S, and PRM on the master device are all

off, indicated that the master device is operating normally.

Figure 12

Figure 12 Connecting Multiple Drives on the Same Network

Table 17 LED Fault Display for CC-Link Option with Multiple Drives

{: On / †: Flashing /

×: Off / ∗: Either on or off

LED Status

Cause

Corrective Action

Master

Remote Device Addresses

(CC-Link Option)

Station 1

Station 2

Station 3

TIME

{

LINE

{

or
TIME

×

LINE

{

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

Normal operation

L.RUN

×

SD

×

RD

×

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

The CC-Link Option for the first station is not properly
installed.

⇒Make sure the CC-Link Option and drive are connected
together properly.

L.RUN

SD

RD

L.ERR

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

The CC-Link Option for the first station is damaged (most
often all LEDs are out).

Note: Sometimes and error will appear on the

drive’s operator

⇒Replace the CC-Link Option.

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN

×

SD

RD

L.ERR

×

L.RUN

×

SD

RD

L.ERR

×

Because L.RUN after Station 2 is off, either the comm. line
between Station 1 and Station 2 is disconnected, or the
terminal block has come loose.

Make sure components are connected correctly, using the
LEDs as a guide to indicate a proper connection.

L.RUN

×

SD

RD

L.ERR

×

L.RUN

×

SD

RD

L.ERR

×

L.RUN

×

SD

RD

L.ERR

×

Comm cable has short-circuited

⇒Look for any short-circuits along the communication lines
and fix any problems.

L.RUN

×

SD

RD

L.ERR

L.RUN

×

SD

RD

L.ERR

L.RUN

×

SD

RD

L.ERR

Comm cable is not wire properly

⇒Check the wiring for the CC-Link Option terminal block
and fix and mistakes.

L.RUN

×

SD

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN

×

SD

RD

{

L.ERR

×

The CC-Link Options for Station 1 and Station 3 have been
assigned the same address.

⇒Enter the correct station address and cycle power.

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN

×

SD

×

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

The CC-Link Option for Station 2 has a different comm speed
setting than the master device.

⇒Set the correct communication speed and cycle power.

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

†

The settings for the CC-Link Option connected to Station 3
were changed without cycling power.

⇒Return any incorrect settings to their original values and
cycle power.

⇒Enter the proper settings and cycle power.

L.RUN

×

SD

×

RD

{

L.ERR

{

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

Parameters related to the CC-Link Option (F6-10, F6-11) for
Station 1 are set outside the acceptable range.

⇒ Set F6-10 and F6-11 correctly and cycle power.

TIME

×

LINE

×

or
TIME

{

LINE

×

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

{

L.RUN {
SD

{

RD

{

L.ERR

×

The CC-Link Option connected to Station 2 is experiencing
noise interference (L.RUN is sometimes off).

⇒Make sure that the CC-Link Options, drives, and master
device are all grounded properly.

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

{

L.RUN {
SD

{

RD

{

L.ERR

{

Noise interference along the cable running between Station 2
and Station 3. (L.RUN is sometimes off)

⇒Reconnect the comm line to the SLD terminal on the CC-
Link Option.
Also make sure that all power cables are properly separated
from comm lines (at least 100 mm away).

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

×

L.RUN {
SD

{

RD

{

L.ERR

{

Terminal resistor not connected.
(L.RUN is sometimes off)

⇒Set up the final station in the series for terminal resistor.

Power
supply

CPU

Master

device

Station 1

DRIVE

Station 2

DRIVE

Station 3

DRIVE

CC-Link

Option

CC-Link

Option

CC-Link

Option