Monitor codes, 10 cc-link code numbers – Yaskawa 1000 Series Drive Option - CC-Link Technical Manual User Manual

Page 28

Advertising
background image

10 CC-Link Code Numbers

28

YASKAWA ELECTRIC SIEP C730600 44A YASKAWA AC Drive-Option Card CC-Link Technical Manual

Monitor Codes

Table 20 Monitor Codes

11FH

Number of pulse 2 speed detection

120H

Fault contents 1

<1>

121H

Fault contents 2

<1>

122H

Fault contents 3

<1>

123H

Fault contents 4

<1>

124H

Fault contents 5

<1>

130H

CPF contents 1

<1>

131H

CPF contents 2

<1>

132H

CPF contents 3

<1>

<1> See

Fault and Minor Fault Contents on page 29

for information on fault contents.

Monitor Code

Name

Comments

0000H

Reserved

0001H

Output frequency

Units are determined by o1-03.

0002H

Output current

Units are either 0.1 A or 0.01 A, depending on the capacity of the drive.

0003H

Output voltage reference

Units: 0.1 V

0004H

Reserved

0005H

Frequency reference

Units are determined by o1-03.

0006H

Motor speed

Units: 1 r/min

0007H

Motor torque

Units: 0.1%

0008H

DC bus voltage

Units: 1 V

0009H

Reserved

000AH

Reserved

000BH

Reserved

000CH

Reserved

000DH

Reserved

000EH

Output power

Units: 0.1 kW

000FH

Input terminal status

0010H

Output terminal status

0011H

Reserved

0012H

Motor excitation current

Units: 0.1%

0013H

Reserved

0014H

Cumulative operation time

• Units: 1 hour
• Parameter o4-02 determines if the operation time is the considered to be whenever the drive powered on or

only when there is voltage output.

0015H

Reserved

0016H

Reserved

0017H

Actual operation time

• Units: 1 hour
• Parameter o4-02 determines if the operation time is the considered to be whenever the drive powered on or

only when there is voltage output.

0018H

Motor secondary current

0019H

Cumulative power

Units: 4 kW

0034H

PID setpoint

Units: 0.1%

0035H

PID input

Units: 0.1%

Command Code

Name

Read

Write

BIT

7

6

5

4

3

2

1

0

Multi-Function Digital Input 1 (terminal S1 enabled)

Multi-Function Digital Input 2 (terminal S2 enabled)

Multi-Function Digital Input 3 (terminal S3 enabled)

Multi-Function Digital Input 4 (terminal S4 enabled)

Multi-Function Digital Input 5 (terminal S5 enabled)

Multi-Function Digital Input 6 (terminal S6 enabled)

Multi-Function Digital Input 7 (terminal S7 enabled)

Multi-Function Digital Input 8 (terminal S8 enabled)

1: ON

RW

0: OFF

7

6

5

4

3

2

1

0

Multi-Function Digital Output (terminal M1-M2) enabled

Multi-Function Digital Output 1 (terminal P1) enabled

Multi-Function Digital Output 2 (terminal P2) enabled

Fault Contact Output (terminal MA/MB-MC) enabled

1: ON

RW

0: OFF

Not used

Advertising