9 troubleshooting – Yaskawa 1000 Series Drive Option - CC-Link Technical Manual User Manual

Page 24

Advertising
background image

9 Troubleshooting

24

YASKAWA ELECTRIC SIEP C730600 44A YASKAWA AC Drive-Option Card CC-Link Technical Manual

Faults that Occur with a Single Drive

The example below demonstrates how to read the LED display on the front cover of the drive to determine the cause of a fault and corrective action.

Figure 11

Figure 11 Connecting a Single Drive

Table 16 LED Fault Display for CC-Link Option with a Single Drive

Note: SD and RD may appear to flash with slower baud rates.

{: On / †: Flashing /

×: Off / ∗: Either on or off

L.RUN

SD

RD

L.ERR

Cause

Possible Solution

{

{

{

×

Normal communications

{

{

{

†

Error has occurred but communication is normal

⇒Remove the source of noise interference.

{

{

×

†

Problem with the hardware

⇒Try cycling the power.
Replace the CC-Link Option if the problem continues.

{

{

×

×

Problem with the hardware

⇒Try cycling the power.
Replace the CC-Link Option if the problem continues.

{

×

{

†

CRC error with the data received, and no response can be
sent

⇒Remove the source of noise interference.

{

×

{

×

No station address received

⇒Check the PLC program and the operation where the problem occurred.

{

×

×

†

Problem with the hardware

⇒Try cycling the power.
Replace the CC-Link Option if the problem continues.

{

×

×

×

Problem with the hardware

⇒Try cycling the power.
Replace the CC-Link Option if the problem continues.

×

{

{

†

A response was received after polling, but a CRC error
occurred when the reflex data was checked

⇒Remove the source of noise interference.

×

{

{

×

Problem with the hardware

⇒Try cycling the power.
Replace the CC-Link Option if the problem continues.

⇒See if the master device is actually set to function as a remote device station.

×

{

×

†

Problem with the hardware

⇒Try cycling the power.
Replace the CC-Link Option if the problem continues.

×

{

×

×

Problem with the hardware

⇒Try cycling the power.
Replace the CC-Link Option if the problem continues.

×

×

{

†

CRC errors occurs when the station address is checked.

⇒Remove the source of noise interference.

×

×

{

×

• No station address
• Cannot receive station address due to noise interference

⇒Remove the source of noise interference.

×

×

×

†

Problem with the hardware

⇒Try cycling the power.
Replace the CC-Link Option if the problem continues.

×

×

×

×

Data cannot be received (CC-Link communications cable
may be disconnected)

⇒Check the wiring.

×

×

{

The station address or communications speed is set
incorrectly

⇒Enter the proper settings and cycle power.

{

{

{

†

The station address or communications speed was changed
without cycling power afterwards.

⇒Return any incorrect settings to their original values and cycle power.

⇒Enter the proper settings and cycle power.

Power
supply

CPU

Master

device

Station 1

DRIVE

CC-Link

Option

Advertising