8 CC-Link Data Table

20

YASKAWA ELECTRIC SIEP C730600 44A YASKAWA AC Drive-Option Card CC-Link Technical Manual

Drive

PLC

Table 10 Remote I/O Table (Drive

PLC)

Note: If making frequent setting changes, use RYD (Frequency Reference 1 flag) for setting the register. Using RYE (Frequency Reference 2 flag) too often can shorten the

performance life of the drive's internal memory.

Remote Register

PLC

Drive

Table 11 Remote Register (PLC

Drive)

Device

Signal Name

Description

Default

RX0

Forward Run

ON: Forward Run Command Present (includes DC Injection Braking)
OFF: No Forward Run Command

RX1

Reverse Run

ON: Reverse Run Command Present
OFF: No Reverse Run Command (includes DC Injection Braking)

RX2

Terminals MA, MB, MC Function

Multi-function output: H2-01

(H2-01 = E: Fault)

RX3

Speed Agree

ON: Output frequency is between frequency reference and the detection width set to L4-02.

RX4

During Stall Prevention

RX5

During Undervoltage

RX6

Terminal P1 Function

Multi-function output: H2-02

(H2-02 = 0: During Run)

RX7

Terminal P2 Function

Multi-function output: H2-03

(H2-03 = 2: Speed Agree 1)

RX8, 9

Reserved

RXA

CC-Link Option Fault

Comm. error between drive and CC-Link device

RXB

Monitoring Motor Revolutions

ON: Currently monitoring motor revolutions.

Data is stored in remote register
RW

R1

.

RXC

Obtain Monitor Data

ON: Monitor data has been updated.

RXD

Frequency Setting Ready 1

ON: Displays the main frequency reference that has been set.

RXE

Frequency Setting Ready 2

ON: Displays the data set to d1-01 (Frequency Reference 1).

Note: Also sets the main frequency reference at the same time.

RXF

Command Code Execute Complete

ON: Displayed after the specified command code has been executed.
RXF signal switches off when the RYF command is no longer present.

RX10

to 19

Reserved

RX1A

Error

ON: Fault occurred on the drive side.

RX1B

Remote Station Ready

ON: Drive is ready to operate.

RX1C to 1F

Reserved

Remote

Register

Name

Description

Request Flag

RW

W0

<1> Refrain from saving data to the EEPROM excessively because the EEPROM used in the drive can only be written to 100,000 times.

Monitor Code

• Sets the code number of the items to be displayed by the monitor. (Refer to

Monitor Codes on page 28

).

• Once the monitor code has been set, the monitor value is stored in register RW

R0

by enabling RYC (the

monitor execute request flag).

• While RW

R0

is updated, RXC (during monitor flag) remains on.

RYC (Monitor Execute Request)

RW

W1

Frequency Setting

• Specifies the source of the frequency reference. The value set to this register becomes the main frequency

reference whenever RYD (frequency setting reference 1) is enabled.

• When RYE (frequency setting reference 2 flag) is enabled, then the value for frequency reference 1 is

written and saved to EEPROM

<1>

.

Note: Parameter o1-03 determines the setting units for the frequency reference.

• RYD (Frequency Reference 1)
• RYE (Frequency Reference 2)

RW

W2

Command Code

• Sets the command code to execute functions such as the fault reset, fault history, parameter read, and so on.

(Refer to

Command Codes on page 26

,

Extended Command Codes on page 27

.)

• When RYF (command code execution request flag) is enabled, the drive executes the specified command.

Once the command has been carried out, RXF switches on.

Note: The value set to RW

W3

(write data) should be adjusted accordingly to match changes to

any parameter settings.

RYF (Command Code Execute
Request)

RW

W3

Write Data

• Sets the value to be used along with RW

W2

(Command Code) as needed.

• RYF (command code execution request flag) needs to be enabled after the command code and write data

have been set.