8 cc-link data table – Yaskawa 1000 Series Drive Option - CC-Link Technical Manual User Manual

Page 21

Advertising
background image

8 CC-Link Data Table

YASKAWA ELECTRIC

SIEP C730600 44A YASKAWA AC Drive-Option Card CC-Link Technical Manual

21

Drive

PLC

Table 12 Remote Register (Drive

PLC)

How o1-03 Determines Data in RW

R1

Table 13 RW

R1

Data

Note: Refer to the technical manual for the drive the CC-Link Option is connected to for more details on parameter settings.

Remote

Register

Name

Description

Check Flag

RW

R0

Monitor Data

• Monitor data is stored according to RW

W0

(Monitor Code).

• Monitor data is updated while RYC (monitor execute request flag) is enabled. RXC (during monitor)

remains on as data is updated.

RXC (while monitoring)

RW

R1

Output Frequency

• Output frequency has been set without any errors. Set in the units specified by o1-03 (Frequency Reference

Setting Units).
Example: When o1-03 = 0, the frequency is displayed in Hz.
When o1-03 = 2, the frequency is displayed as r/min.

• When operating not in V/f or OLV for PM, the motor revolutions are stored as r/min. Here, RXB (actual

motor rotations) is enabled.

• When RYB (motor rotations / output frequency switch) is enabled, the value stored to this register changes

from the number motor rotations to the output frequency.

RW

R2

Response Code

• Sets 00H when there are no problems with RW

W2

(Command Code) and RW

W3

(Write Data).

• Sets 01H through 03H if an error occurs.
• Response Code:

00h: Normal
01h: Write-mode error (attempted to write during run, etc.)
02h: Command code error
03h: Data setting range error

RXF (Command Code Execute
Complete)

RW

R3

Read Data

Data is set according to the command code.

Frequency Reference Setting and Display Units

(o1-03)

Frequency Reference Data Contents (RW

R1

)

0

Hz (output frequency)

1

% (percent of maximum output frequency)

2

min

-1

(calculated from the maximum output frequency and the number of motor poles)

3

User-set (according to parameter o1-10 and o1-11)

Advertising