6 CC-Link Option Drive Parameters

6

CC-Link Option Drive Parameters

Confirm proper setting of the all parameters in

Table 6

before starting network communications.

Table 6 Parameter Settings

No.

Name

Description

Default

b1-01

<1>

<1> To start and stop the drive with the CC-Link master device using serial communications, set b1-02 to “3”. To control the frequency reference of the drive via the master device, set b1-01

to “3”.

<2> If set to 3, then the drive will continue to operate when a fault is detected. Take proper measures such as installing an emergency stop switch.

<3> The drive default setting is 2.0 s, but this default setting will automatically be changed to 0.0 s when CC-Link option is connected.

<4> Enabled in CLV, PM OLV 2, and PM CLV control modes (A1-02 = 3, 6, or 7). When enabled, d5-01 determines whether the value is read as the torque limit value (d5-01 = 0) or read as

the torque reference value (d5-01 = 1). In Closed Loop Vector for PM motors, this value is read as the torque limit.

<5> Default setting specifies that the torque reference or torque limit is to be provided via network communications (F6-06 = 1). The motor may not rotate if no torque reference or torque

limit is supplied from the PLC.

<6> Power must be cycled in order for any setting changes to take affect.

<7> All station addresses must be unique. If set to 0, the L.ERR light will turn on and a Station Address Error (AEr) will occur.

<8> A total of 42 nodes can be connected, assuming that all connections are inverter drives.

The following conditions apply when connecting devices that are not drives to the network:

Frequency Reference Selection

Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS communications
3: Option PCB
4: Pulse Input (Terminal RP)

1

b1-02

<1>

Run Command Selection

Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S7
2: MEMOBUS communications
3: Option PCB

1

F6-01

Operation Selection after
Communications Error

Determines drive response when a bUS error is detected during communications with the CC-Link Option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

1

F6-02

External Fault Detection Conditions
(EF0)

Sets the condition for external fault detection (EF0)
0: Always detected.
1: Detected only during operation.

0

F6-03

Stopping Method for External Fault
from Communication Option

Determines drive response for external fault input (EF0) detection during CC-Link communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<2>

1

F6-04

<6>

bUS Error Detection Delay Time

Set the maximum time the drive should wait for a communication error to occur (bUS).
Range 0.0 to 5.0 s

0.0 s

<3>

F6-06

<4>

Torque Reference/Torque Limit
Selection from Communications
Option

0: Torque reference / torque limit via network communications are disabled.
1: Torque reference / torque limit via network communications are enabled.

<5>

0

F6-07

NetRef/ComRef Selection Function

0: Multi-step speed reference disabled (F7 mode)
1: Multi-step speed reference allowed (V7 mode)

1

F6-08

Reset Communication Related
Parameters

Determines which communication-related parameters are set back to their original default values when the drive is
initialized.
0: Do not reset F6-†† and F7-†† parameters when the drive is initialized using parameter A1-03.
1: Rest F6-†† and F7-†† parameters when the drive is initialized using parameter A1-03.

Note: Setting this parameter does not affect communication-related parameters.

0

F6-10

<6>

Station Address

<7> <8>

0 to 64

0

F6-11

<6>

Comm Speed

0: 156 kbps
1: 625 kbps
2: 2.5 Mbps
3: 5 Mbps
4: 10 Mbps

0

F6-14

bUS Error Auto Reset

0: Disabled
1: Enabled

0

A: number of remote I/O nodes........ 64 max
B: number of remote device nodes... 42 max
C: number of local nodes.................. 26 max

a: number of units that occupies 1 node

b: number of units that occupies 2 nodes

c: number of units that occupies 3 nodes d:

number of units that occupies 4 nodes

{(1×a)+(2×b)+(3×c)+(4×d)} ≦64

{(16×A)+(54×B)+(88×C)} ≦2304

(

(

)

)