9 troubleshooting, Drive-side error codes, 9troubleshooting – Yaskawa 1000 Series Drive Option - CC-Link Technical Manual User Manual

Page 22

Advertising
background image

22

YASKAWA ELECTRIC SIEP C730600 44A YASKAWA AC Drive-Option Card CC-Link Technical Manual

9 Troubleshooting

9

Troubleshooting

Drive-Side Error Codes

Drive-side error codes appear on the drive’s operator. Causes of the errors and corrective actions are listed in

Table 14

.

For additional error codes that may appear on the operator screen, refer to the technical manual for the drive the CC-Link Option is connected to.

Faults

Both bUS (CC-Link Option Communication Error) and EF0 (External Fault Input from the CC-Link Option) can appear as an alarm or as a fault.

When a fault occurs, the digital operator ALM LED remains. When an alarm occurs, the digital operator ALM LED flashes.
If communication stops while the drive is running, answer the following questions to help remedy the fault:

• Is the CC-Link Option properly installed?

• Is the communication line properly connected to the CC-Link Option? Is it loose?

• Is the PLC program working? Has the PLC CPU stopped?

• Did a momentary power loss interrupt communications?

Table 14 Fault Display and Possible Solutions

Operator Display

Fault Name

bUS

CC-Link Option Communication Error
After establishing initial communication, the connection was lost.
Only detected when the run command or frequency reference is assigned to the option (b1-03 = 3 or b1-02 = 3).

Cause

Possible Solution

Master controller (PLC) has stopped communicating.

Check for faulty wiring.

⇒ Correct any wiring problems.

Communication cable is not connected properly.

A data error occurred due to noise

Check the various options available to minimize the effects of noise.

⇒ Take steps to counteract noise in the control circuit wiring, main circuit lines, and ground wiring.

⇒ If a magnetic contactor is identified as a source of noise, install a surge absorber to the contactor coil.

⇒ Use cables recommended by Yaskawa, or another type of shielded line. The shield should be grounded on the PLC side and
on the CC-Link Option side.

CC-Link Option is damaged.

⇒ If there are no problems with the wiring and the error continues to occur, replace the CC-Link Option.

Operator Display

Fault Name

EF0

External Fault Input from CC-Link Option
The alarm function for an external device has been triggered.

Cause

Possible Solution

An external fault is being sent from the master controller
(PLC).

⇒ Remove the cause of the external fault.

⇒ Reset the external fault input from the PLC device.

Problem with the PLC program

⇒ Check the program used by the PLC and make the appropriate corrections.

Operator Display

Fault Name

oFA00

CC-Link Option Fault (CN5-A)
CC-Link Option is not properly connected.

Cause

Possible Solution

Non-compatible option connected to the drive

⇒ Connect an option that is compatible with the drive.

Operator Display

Fault Name

oFA01

CC-Link Option Fault (CN5-A)
CC-Link Option is not properly connected.

Cause

Possible Solution

Problem with the connectors between the drive and CC-
Link Option

⇒ Turn the power off and check the connectors between the drive and CC-Link Option.

Operator Display

Fault Name

to

oFA30 to oFA43

CC-Link Option Fault (CN5-A)

Communication ID error

Cause

Possible Solution

CC-Link Option hardware fault

⇒ Replace the CC-Link Option. Contact Yaskawa for assistance.

Operator Display

Fault Name

oFb00

CC-Link Option Fault (CN5-B)
Non-compatible option card is connected.

Cause

Possible Solution

Non-compatible option connected to the drive.

⇒ Connect the correct option card to CN5-A.

Advertising