Three-phase 400 v class, I.3 electrical installation safety – Yaskawa AC Drive Z1000 HVAC User Manual

Page 21

Advertising
background image

Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb. in.)

2A0343

<1>

R/L1, S/L2, T/L3

4/0 × 2

3/0 to 350

M12

32.0 to 40.0

(283 to 354)

U/T1, V/T2, W/T3

4/0 × 2

–, +1

+3

M10

18.0 to 23.0

(159 to 204)

M12

32.0 to 40.0

(283 to 354)

2A0396

<1>

R/L1, S/L2, T/L3

250 × 2

3/0 to 350

M12

32.0 to 40.0

(283 to 354)

U/T1, V/T2, W/T3

250 × 2

–, +1

+3

M10

18.0 to 23.0

(159 to 204)

M12

32.0 to 40.0

(283 to 354)

<1> Drive models 2A0046 to 2A0396 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools recommended by the

terminal manufacturer for crimping.

n

Three-Phase 400 V Class

Table i.5 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)

Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

4A0005
4A0008
4A0011

R/L1, S/L2, T/L3

14

14 to 8

M4

1.6 to 1.8

(14 to 16)

U/T1, V/T2, W/T3

14

-M, +M

M5

2.7 to 3.0

(24 to 27)

4A0014

R/L1, S/L2, T/L3

12

14 to 8

M4

1.6 to 1.8

(14 to 16)

U/T1, V/T2, W/T3

12

-M, +M

M5

2.7 to 3.0

(24 to 27)

4A0021

R/L1, S/L2, T/L3

10

14 to 8

M4

1.6 to 1.8

(14 to 16)

U/T1, V/T2, W/T3

10

-M, +M

M5

2.7 to 3.0

(24 to 27)

4A0027

R/L1, S/L2, T/L3

8

14 to 8

M4

1.6 to 1.8

(14 to 16)

U/T1, V/T2, W/T3

8

-M, +M

M5

2.7 to 3.0

(24 to 27)

4A0034

<1>

R/L1, S/L2, T/L3

8

10 to 4

M5

2.7 to 3.0

(24 to 27)

U/T1, V/T2, W/T3

8

-M, +M

4A0040

<1>

R/L1, S/L2, T/L3

8

10 to 4

M5

2.7 to 3.0

(24 to 27)

U/T1, V/T2, W/T3

8

-M, +M

4A0052

<1>

R/L1, S/L2, T/L3

6

8 to 2/0

M8

5.4 to 6.0

(48 to 53)

U/T1, V/T2, W/T3

6

-M, +M

i.3 Electrical Installation Safety