Wiring the control circuit terminal, Figure i.15, Serial communication terminals – Yaskawa AC Drive Z1000 HVAC User Manual

Page 30: Wire size and torque specifications

Advertising
background image

A

B

C

D

A – External power, 48 V max.
B – Suppression diode

C – Coil
D – 50 mA or less

Figure i.15 Connecting a Suppression Diode

n

Serial Communication Terminals

Table i.11 Control Circuit Terminals: Serial Communications

Type

No.

Signal Name

Function (Signal Level)

Serial Communication

(APOGEE FLN,

BACnet, MEMOBUS/

Modbus, or Metasys
N2)

<1>

R+

Communications input (+)

APOGEE FLN, BACnet, MEMOBUS/

Modbus, or Metasys N2 communication: Use

an RS-422 or RS-485 cable to connect the

drive.

• APOGEE FLN

Comm. RS-422/

RS-485, 4.8 kbps

• BACnet Comm.

RS-485, max. 76.8

kbps

• MEMOBUS/

Modbus Comm.

RS-422/RS-485,

max. 115.2 kbps

• Metasys N2 Comm.

RS-422/RS-485, 9.6

kbps

R-

Communications input (-)

S+

Communications output (+)

S-

Communications output (-)

IG

Communications ground

0 V

FE

Option card ground

<1> Enable the termination resistor in the last drive in an APOGEE FLN, BACnet, MEMOBUS/Modbus, or Metasys N2 network by setting DIP switch

S2 to the ON position. Refer to the Z1000 User manual TOEPC71061645 for more information on the termination resistor.

n

Wire Size and Torque Specifications

Select appropriate wire type and gauges from

Table i.12

. For simpler and more reliable wiring, use crimp ferrules on the wire

ends. Refer to the Z1000 User manual TOEPC71061645 for ferrule terminal types and sizes.

Table i.12 Wire Gauges

Terminal

Screw

Size

Tightening

Torque

N

m

(lb. in)

Bare Wire Terminal

Ferrule-Type Terminal

Wire Type

Applicable

wire size

mm

2

(AWG)

Recomm.

wire size

mm

2

(AWG)

Applicable

wire size

mm

2

(AWG)

Recomm.

wire size

mm

2

(AWG)

S1-S7, SC, SN, SP

M3

0.5 to 0.6

(4.4 to 5.3)

Stranded wire:

0.2 to 1.0

(24 to 16)

Solid wire:

0.2 to 1.5

(24 to 16)

0.75 (18)

0.25 to 0.5

(24 to 20)

0.5 (20)

Shielded wire,

etc.

+V, A1, A2, AC
MA, MB, MC
M1-M6
FM, AM, AC
R+, R-, S+, S-, IG

u

Wiring the Control Circuit Terminal

This section describes the proper procedures and preparations for wiring the control terminals.

WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on. Failure to comply could result

in death or serious injury.

NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, -M, +M, -, +1, +3, U/T1, V/T2, W/T3) and other

high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference.

NOTICE: Separate wiring for digital output terminals MA, MB, MC, and M1 to M6 from wiring to other control circuit lines. Improper wiring

practices could result in drive or equipment malfunction or nuisance trips.

NOTICE: Use a class 2 power supply when connecting to the control terminals. Improper application of peripheral devices could result in

drive performance degradation due to improper power supply. Refer to NEC Article 725 Class 1, Class 2, and Class 3 Remote-Control,

Signaling, and Power Limited Circuits for requirements concerning class 2 power supplies.

i.3 Electrical Installation Safety

30

YASKAWA ELECTRIC TOEP YAIZ1U 01A YASKAWA AC Drive – Z1000 Safety Precautions