Drive specifications – Yaskawa AC Drive Z1000 HVAC User Manual

Page 47

Advertising
background image

u

Drive Specifications

Item

Specification

Control

Character-

istics

Control Method

The following control methods can be set using drive parameters:
• V/f Control (V/f)
• Open Loop Vector Control for PM (OLV/PM)

Frequency Control Range 0.01 to 240 Hz

Frequency Accuracy

(Temperature Fluctuation)

Digital input: within ±0.01% of the max output frequency (-10 to +50 °C [14 to 122 °F])

Analog input: within ±0.1% of the max output frequency (25 °C ±10 °C [77 ±50°F])

Frequency Setting

Resolution

Digital inputs: 0.01 Hz

Analog inputs: 1/1000 of the maximum output frequency setting (10 bit unsigned)

Output Frequency

Resolution

0.001 Hz

Frequency Setting Signal 0 to 10 V, 0 to 20 mA, 4 to 20 mA

Starting Torque

<1>

V/f: 140% at 3 Hz

OLV/PM: 50% at 6 Hz

Speed Control Range

<1>

V/f: 1:40

OLV/PM: 1:20

Speed Response

<1>

OLV/PM: 10 Hz

Accel/Decel Time

0.0 to 6000.0 s (4 selectable combinations of independent acceleration and deceleration settings)

Braking Torque

Approximately 20%

V/f Characteristics

User-selected programs and V/f preset patterns possible

Main Control Functions

Momentary Power Loss Ride-Thru, Speed Search, Overtorque/Undertorque Detection, 4 Step Speed

(max), Accel/Decel Switch, S-curve Accel/decel, 3-Wire Sequence, Auto-Tuning (Stationary for Line-to-

Line Resistance, Rotational for V/f Control), Cooling Fan on/off Switch, Slip Compensation, Torque

Compensation, Frequency Jump, Upper/lower Limits for Frequency Reference, DC Injection Braking at

Start and Stop, Overexcitation Braking, High Slip Braking, PI Control (with sleep function), Energy Saving

Control, APOGEE FLN Comm. (RS-422/RS-485 4.8 kbps), BACnet Comm. (RS-485 max. 76.8 kbps),

MEMOBUS/Modbus Comm. (RS-422/RS-485 max, 115.2 kbps), Metasys N2 Comm. (RS-422/RS-485

9.6 kbps), Fault Restart, Application Presets, KEB, Overexcitation Deceleration, Overvoltage Suppression,

Sequence Timer Operation, Secondary PI Control, Bypass Operation, HOA Keypad, Dynamic Noise

Control

Protection

Functions

Motor Protection

Electronic thermal overload relay

Momentary Overcurrent

Protection

Drive stops when rated output current exceeds 175%

Overload Protection

Drive stops after 60 s at 110% of rated output current

<2>

Drive stops after 0.5 s at 140% of rated output current

<2>

Overvoltage Protection

200 V class: Stops when DC bus voltage exceeds approx. 410 V

400 V class: Stops when DC bus voltage exceeds approx. 820 V

i.6 European Standards

YASKAWA ELECTRIC TOEP YAIZ1U 01A YASKAWA AC Drive – Z1000 Safety Precautions

47