Yaskawa AC Drive Z1000 HVAC User Manual

Page 48

Advertising
background image

Item

Specification

Protection

Functions

Undervoltage Protection

200 V class: Stops when DC bus voltage falls below approx. 190 V

400 V class:

Stops when DC bus voltage falls below approximately 350 V when using an input voltage lower than 400V

Stops when DC bus voltage falls below approximately 380 V when using an input voltage lower than 460

V

Stops when DC bus voltage falls below approximately 440 V when using an input voltage of 460 V or

higher

Momentary Power Loss

Ride-Thru

Immediately stop after 15 ms or longer power loss

<3>

Continuous operation during power loss shorter than 2 s by speed search function

<4>

Heatsink Overheat

Protection

Thermistor

Stall Prevention

Stall Prevention is available during acceleration, deceleration, and during run.

Ground Protection

Electronic circuit protection

<5> <6>

DC Bus Charge LED

Remains lit until DC bus voltage falls below 50 V

Environment

Area of Use

Indoors

Ambient Temperature

-10 °C to +40 °C (14 to 104 °F) IP20/NEMA Type 1 Enclosure, External Heatsink (2A0011 to 2A0273

and 4A0005 to 4A0302)

-10 °C to +50 °C (14 to 122 °F) IP00/Open Type Enclosure (2A0343 and 2A0396, and 4A0361 to 4A0590)

Note:

1. To install a heatsink on the outside of a panel, design the panel to keep the air temperature

inside the panel within 10 °C (5 °C for 2A0273 and 4A0124) of the outside air

temperature.

2. Ambient temperature range for continuous operations is -10 to +40 °C (14 to 104 °F)

when external heatsink installation method is applied for models 2A0343 and 2A0396

and 4A0361 to 4A0590.

Humidity

95% RH or less (no condensation)

Storage Temperature

-20 °C to +70 °C (-4 to +158 °F) (short-term temperature during transportation)

Altitude

Up to 1000 meters without derating, up to 3000 m with output current and voltage derating.

Refer to

Altitude Derating on page 46

for details.

Vibration/Shock

10 to 20 Hz at 9.8 m/s

2

20 to 55 Hz at 5.9 m/s

2

(2A0011 to 2A0031 and 4A0005 to 4A0027) or

2.0 m/s

2

(2A0046 to 2A0396 and 4A0034 to 4A0590)

Standards

IEC/EN 61800-5-1

Protection Design

IP00/Open Type enclosure, IP20/NEMA Type 1 enclosure

<7>

<1> The accuracy of these values depends on motor characteristics, ambient conditions, and drive settings. Specifications may vary with different motors

and with changing motor temperature. Contact Yaskawa for consultation.

<2> Overload protection may be triggered when operating with 100% of the rated output current if the output frequency is less than 6 Hz.
<3> May be shorter due to load conditions and motor speed.
<4> A 24 V power supply Unit (Model Nos. PS-A10LB, PS-A10HB) is required for models 2A0011 to 2A0059 and 4A0005 to 4A0052 if the application

must continue running for up to 2 seconds during a momentary power loss.

<5> Ground protection cannot be provided when the impedance of the ground fault path is too low, or when the drive is powered up while a ground

fault is present at the output.

<6> Setting L8-09 to 1 enables ground fault detection in models 2A0075 to 2A0396 and 4A0052 to 4A0590.
<7> Drive models 2A0011 to 2A0273 and 4A0011 to 4A0302 are designed to IP20/NEMA Type 1 specifications with a protective cover on the top.

Removing this top protective cover voids the NEMA Type 1 protection while maintaining IP20 conformity; removing the bottom conduit bracket
voids the NEMA Type 1 protection and IP20 conformity.

i.6 European Standards

48

YASKAWA ELECTRIC TOEP YAIZ1U 01A YASKAWA AC Drive – Z1000 Safety Precautions