Sinking/Sourcing Mode Switch for Digital Inputs

Use the wire jumper between terminals SC and SP or SC and SN to select between Sink mode, Source mode or external power

supply for the digital inputs S1 to S7 as shown in

Table i.13

(Default: Sink mode, internal power supply).

NOTICE: Do not short terminals SP and SN. Failure to comply will damage the drive.

Table i.13 Digital Input Sink/Source/External Power Supply Selection

Mode

Drive Internal Power Supply

(Terminals SN and SP)

External 24 Vdc Power Supply

Sinking Mode (NPN)

SC

S7

S6

24 Vdc

SP

SN

SC

S7

S6

24 Vdc

SP

SN

External

24 Vdc

Sourcing Mode (PNP)

SC

S7

S6

24 Vdc

SP

SN

SC

S7

S6

24 Vdc

SP

SN

External

24 Vdc

u

Input Signal Selection for Terminals A1 and A2

Terminals A1 and A2 can be used to input either a voltage or a current signal. Select the signal type using jumper S1 as

explained in

Table i.14

. Set parameters H3-01 and H3-09 accordingly as shown in

Table i.15

.

Note:

If terminals A1 and A2 are both set for frequency bias (H3-02 = 0 and H3-10 = 0), both input values will be combined to create the frequency

reference.

Table i.14 Jumper S1 Settings

Terminal

Voltage Output

Current Output

Terminal A1

A2

A1

V

I

A2

A1

V

I

Terminal A2

A2

A1

V

I

A2

A1

V

I